REFRIGER NT CONNECTIONS
All units are factory charged with Refrigerant R-410A. All models are supplied with
service valves. Keep tube ends sealed until connection is to be made to prevent
system contamination.
TOOLS REQUIRED FOR INST LLING &
SERVICING R-410 MODELS
Manifold Sets:
-Up to 800 PSIG High side
-Up to 250 PSIG Low Side
-550 PSIG Low Side Retard
Manifold Hoses:
-Service Pressure Rating of 800 PSIG
Recovery Cylinders:
-400 PSIG Pressure Rating
-Dept. of Transportation 4BA400 or BW400
C UTION
R-410A systems operate at higher pressures than R-22 systems. Do not use
R-22 service equipment or components on R-410A equipment.