8.9.9

Pump management

The Pump management menu is used to set how the circulation
pump will be controlled.
To select the Pump management control function, do this:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > Control settings > Advanced
control > Pump management
Example screen:
2. Select one of the following alternatives:
Internal ctrl
This alternative lets the Climate Controller C-46 fully
control the circulation pump.
Bus
This alternative is used when the circulation pump is
controlled from the Controller C-56 Radio through the
bus.
Always on
This alternative is used to set the circulation pump always
running.
Always off
This alternative means that the circulation pump is not
controlled by the climate system.
In this case it must be controlled by an external source,
for example an on-off switch.

8.10 ECO mode

The default setting in the Climate Controller C-46 is comfort
(COMF) mode. In comfort mode the system keeps a constant
temperature in the room at the setpoint temperature. If an indoor
thermostat is connected to the Climate Controller C-46, then the
indoor setpoint temperature is used. In all other cases the supply
setpoint temperature is used.
In economy (ECO) mode, the temperature setpoint is
automatically set back for periods of the day when the comfort
temperature is not needed, for example during the night or when
no one is present in the house.
For more information about ECO profiling, see section
Economy and comfort modes, page
This section describes how to make all settings necessary for the
switching between comfort and economy modes.
To display the ECO mode menu:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > ECO mode
Example screen:
34
10.1
44.
2. In the ECO mode menu, select the required item and press
OK.
Heating, proceed with section
Cooling, proceed with section
8.10.1

Heating

To display the Heating menu under ECO mode:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > ECO mode > Heating
Example screen:
2. In the Heating menu, select the required item and press OK.
Note: Items in the list below depend on the selected
operating mode and system configuration.
Supply temp. setback,
, page 34
Apply ECO profiles,
, page 35
Edit ECO profiles,
, page 35
Supply temp. setback
This function can be used when an Interface I-76 is connected to
a Controller C-56 Radio, which in its turn is connected to the
Climate Controller C-46. In this case the Interface I-76 controls
the switching from comfort to economy mode and back, but the
Climate Controller C-46 controls the supply temperature setback.
To modify the temperature setback:
1. Navigate through the screens using the navigation keys:
Uponor > Main menu > ECO mode > Heating >
Supply temp. setback
Example screen:
2. Select the amount of supply temperature setback and press
OK.
Default setting: 2 °C
Setting range: 0–10 °C
Setting accuracy: 1 °C
CLIMATE CONTROLLER C-46 - INSTALLATION AND OPERATION MANUAL
8.10.1, page
34.
8.10.2, page
36.