Mitsubishi Electric Lossnay VL-100U5-E Handbook page 14

Hide thumbs Also See for Lossnay VL-100U5-E:
Table of Contents

Advertisement

(8) Air supply (SA) fan
1 Unscrew the motor fix plate clamping screw (one PTT screw 4 ×
14, indicated by ).
2 Turn the motor fix plate upside down, and put it on the main unit.
3 Remove the special nut (8) and tab washer, and then remove
the SA fan.
4 Remove the special (spl) washer (8) (16 mm in outer diameter).
Reassembly precaution
Be aware of the size difference between each washer for EA
fan and SA fan.
Incorrect installation may cause unusual noise.
(9) Motor
• Unscrew the screws that clamps motor and lead cover (six PTT
screws 4 × 10, indicated by ), and then remove the motor.
Reassembly precaution
When installing the lead cover, make sure to place it under the
motor (indicated by ).
─ 14 ─
Motor fix plate
SA fan
Special nut (8)
Tab washer
Spl washer (8)
Lead cover
Motor