Mitsubishi Electric Mr.SERVICE PUHZ-HRP71VHA Service Manual page 32

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.SERVICE PUHZ-HRP71VHA:
Table of Contents

Advertisement

11-3-4. Malfunction-diagnosis method by wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<
Malfunction-diagnosis method at maintenance service>
CHECK
CHECK
display
ON/OFF
TEMP
ON/OFF
button
AUTO STOP
FAN
AUTO START
MODE
VANE
CHECK LOUVER
CHECK
TEST RUN
button
RESET
SET
CLOCK
[Procedure]
1. Press the CHECK button twice.
Refrigerant
address
display
2. Press the temperature
Temperature
buttons.
button
3. Point the remote controller at the
HOUR
sensor on the indoor unit and
button
h
press the HOUR button.
min
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
• "CHECK" lights, and refrigerant
address "00" blinks.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit's DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit-
tent buzzer sound, the operation lamp
blinks, and the error code is output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
32

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents