6

DATA

6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
Service Ref.
PUHZ-HRP71VHA
PUHZ-HRP71VHA2
PUHZ-HRP71VHA2R1
PUHZ-HRP100VHA(2)
PUHZ-HRP100YHA(2)
PUHZ-HRP100VHA2R1
PUHZ-HRP100YHA2R1
PUHZ-HRP125YHA
PUHZ-HRP125YHA2
PUHZ-HRP125YHA2R1
6-2. COMPRESSOR TECHNICAL DATA
Service Ref.
Compressor model
U-V
Winding
U-W
Resistance
(
)
W-V
Service Ref.
Compressor model
U-V
Winding
U-W
Resistance
(
)
W-V
30m
10m
20m
5.1
5.3
5.5
5.1
5.3
5.5
5.1
5.3
5.5
PUHZ-HRP71VHA
PUHZ-HRP100VHA
ANB33FJCMT
0.188
0.188
0.188
PUHZ-HRP71VHA2
PUHZ-HRP100VHA2
PUHZ-HRP71VHA2R1
PUHZ-HRP100VHA2R1
ANB33FJEMT
0.188
0.188
0.188
Piping length (one way)
40m
50m
6.1
6.7
6.1
6.7
6.1
6.7
For pipe longer than 30m, additional charge
is required.
(at 20 )
PUHZ-HRP100YHA
PUHZ-HRP125YHA
ANB33FJBMT
0.302
0.302
0.302
(at 20 )
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
PUHZ-HRP100YHA2R1
PUHZ-HRP125YHA2R1
ANB33FJDMT
0.302
0.302
0.302
9
Factory
charged
60m
75m
7.3
7.9
7.3
7.9
7.3
7.9
5.5
5.5
5.5