9-3. INDOOR – OUTDOOR CONNECTING CABLE
The cable shall not be lighter than design 60245 IEC or 60227 IEC.
Outdoor power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
The max. cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor/Outdoor separate
power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
The optional indoor power supply terminal kit is necessary.
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient
insulation to ground or a poor electrical contact at the intermediate connection point.
Max. 45m
Max. 50m
3
1.5 (polar)
3
2.5 (polar)
1
Min. 1.5
1
22
Wire No.
Size (
3
2.5 (polar) and S3 separated
Min. 2.5
Wire No.
Size (
Max. 120m
2
Min. 0.3
)
Max. 80m
1
Min. 2.5
)