3.2 Domestic hot water heating with cylinder loading system

3.2 Domestic hot water heating with cylinder loading system
The Viessmann cylinder loading system is
a combination comprising a Vitocell-L
storage cylinder and a Vitotrans 222 heat
exchanger kit. The cylinder loading sys
tem for domestic hot water applications
is particularly suitable for use in conjunc
tion with:
H large cylinder storage capacities involv
ing staggered loading and withdrawal
times, e.g. hot water draw-off at peak
times in schools, sports centres, hospi
tals, barracks, institutional buildings
etc.
Vitocell-L 100/300
Connectors
%
Cylinder temperature sensor, top
(terminals "1" and "2")
%
Cylinder temperature sensor,
bottom (terminals "2" and "3")
aJ B
Temperature sensor, Vitotrans 222
sÖ A 1 Primary pump connection in
cylinder loading system
sA
Secondary pump connection in
cylinder loading system
sK
DHW circulation pump (not with
Vitotronic 100)
gS A 1 3-port valve, Vitotrans 222
Notes on the circuit diagrams (in section 3.1)
Circuit diagram 3 to 7 (multi-boiler systems)
The heat exchanger kit Vitotrans 222
is controlled through the Vitotronic 333.
42
H heating systems for which low return
temperatures are required or in which
return temperatures are limited, e.g.
district heating systems or condensing
boilers.
The wide temperature range on the do
mestic hot water side produces a low
return temperature, providing the bene
fit of almost total condensing in the
case of condensing technology.
28
1
5
5
21
17 B
52 A1
20 A1
Vitotrans 222
(heat exchanger kit)
System-specific coding on the Vitotronic
1
Change "4C" to "1" use of connector sÖ
as primary pump for heat exchanger kit.
Change "4E" to "1" use of output gS as
primary control for heat exchanger kit.
Change "55" to "3" use of cylinder con
trol unit for heat exchanger kit.
H short periods of peak output, i.e. high
hot water drawing rates and different
re-heating times, e.g. domestic hot
water heating for indoor swimming
pools, sports centres, industrial plants
etc.
H limited space, as the cylinder loading
system can transfer high outputs.
The cylinder loading system can be con
trolled by a 1 Vitotronic 100, 200, 300,
333 or 050.
Boiler
Please note:
The cylinder loading system can be con
trolled through the Vitotronic 100, 200,
300 or 333. If none of these control units
is installed or if two or more cylinder
loading systems are installed, a mixing
valve control of the Vitotronic 050 (Type
HK1W or HK3W) can also be used for
control purposes.