Auto Restart Control; Indication Panel; Ha Terminal (Hajem-A) - Panasonic CS-RE18PKR Service Manual

Hide thumbs Also See for CS-RE18PKR:
Table of Contents

Advertisement

12.10 Auto Restart Control

1
When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within
three to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be
selected randomly) after power supply resumes.
2
This type of control is not applicable during ON/OFF Timer setting.
3
This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.

12.11 Indication Panel

LED
Color
Light ON
Light OFF
Note:
If POWER LED is blinking, the possible operation of the unit are Hot Start, during Deice operation, operation
mode judgment, or ON timer sampling.
If Timer LED is blinking, there is an abnormality operation occurs.

12.12 HA Terminal (HAJEM-A)

Enable digital connection from indoor unit to external devices.
Control items:
1
Start/stop input.
2
Start/stop signal output.
Condition
1
1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal.
(1 pulse signal: shortage status 200 ~ 300 msec)
2
3-4 (Static output): 5V output during the unit ON. No output at OFF.
POWER
Green
Operation ON
Timer Setting ON
Operation OFF
Timer Setting OFF
TIMER
QUIET/ECONOMY
Orange
Orange
Quiet/Economy Mode ON
Quiet/Economy Mode OFF
56
POWERFUL
Orange
Powerful Mode ON
Powerful Mode OFF