14
en | Programming
Temperature
rate-of-rise [K
min
10
20
30
F.01U.003.448 | 8.0 | 2011.10
Response time for detectors in the
sensitivity class A1R
-1
Lower limiting
]
value [min/sec]
1 min
30 s
20 s
Operation Guide
Automatic Fire Detectors LSN improved
Response time for detectors in the
sensitivity classes A2R/BR
Upper limiting
Lower limiting
value [min/sec]
value [min/sec]
4 min 20 s
2 min
2 min 20 s
1 min
1 min 40 s
Upper limiting
value [min/sec]
5 min 30 s
3 min 13 s
40 s
2 min 25 s