Detector Type Encoding; Test Instructions For Lsn Improved Version Fire Detectors; Test Instructions For All Fire Detectors With Optical Sensor - Bosch FAP-DO420 Operation Manual

Automatic fire detectors lsn improved version
Hide thumbs Also See for FAP-DO420:
Table of Contents

Advertisement

Automatic Fire Detectors LSN improved
version
8.2

Detector Type Encoding

With the exception of the FAP-O 420 and FAP-O 420-KKW, all detectors are fitted with a
colored ring around the central individual display to identify the detector type.
This facilitates inspection by service personnel.
Type number
FAP-DOTC420
FAP-OTC 420
FAP-DOT420
FAP-OT 420
FAH-T 420
FAH-T 420-KKW
FAP-DO420
FAP-O 420
FAP-O 420-KKW
8.3

Test Instructions for LSN improved version Fire Detectors

The latest generation of FAP-DOTC420 / FAP-OTC 420 Multisensor Detectors is equipped with
an additional sensor for detecting CO in the event of a fire. The CO sensor provides improved
response behavior and increased malfunction suppression in critical environmental
conditions.
For fire detection, detectors use the time behavior of the fire characteristics, which deviates
significantly from the time behavior of disturbance variables and also from the time behavior
of a detector check with aerosol.
Therefore, for a functional test, the detector must be switched to revision mode.
8.3.1

Test Instructions for All Fire Detectors With Optical Sensor

NOTICE!
The test head must remain over the detector until the detector has been triggered. The
distribution of the test aerosol in the transceiver and thus the trigger time of the sensor can
take up to 10 seconds.
Testing outside the Revision Mode
If you want to test detectors in controls, 2-detector or 2-goup dependencies, you must test
them outside the revision mode. Proceed as follows:
Bosch Sicherheitssysteme GmbH
Color code
2 x yellow
Yellow
2 x black
Black
2 x gray
On the fire panel, switch the detector zone to be inspected to revision mode. Thus the
detector is set automatically into revision operation and prepared for the detector test.
Only in walktest mode can the detector's individual sensors be made to trigger one after
the other with the corresponding test device. For this, you should use the service
accessories we recommend.
The optical sensor is tested with the detector tester for smoke detectors with the Solo
A3-001 Test Aerosol.
FAP-0 420 and FAP-DO420
Trigger the detector with a testing aerosol. Depending on the sensitivity settings, it can
take up top 1 minute till the detector goes off. It is recommended to apply the aerosol in
spurts (for example one short spurt of 1 second, 30 seconds of waiting, another short
spurt).
Operation Guide
Red
Red
-
-
Maintenance and Service | en
F.01U.003.448 | 8.0 | 2011.10
37