Explorer II Medium Wood Stove
B. Clearances to Combustibles
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction
H
G
I
F
E
INSTALLATION: FULL VERTICAL AND ALCOVE
SINGLE WALL PIPE
DOUBLE WALL PIPE
INSTALLATION: 90° ELBOW OFF TOP OF STOVE THROUGH BACKWALL
DOUBLE WALL PIPE ONLY
INSTALLATION: HORIZONTAL THRU WALL
SINGLE WALL PIPE
INSTALLATION: ALCOVE - Six inch (6 inches) (152mm) diameter listed SINGLE WALL or DOUBLE WALL air insulat-
ed connector pipe with UL 103 HT listed factory-built Class "A" chimney, or a masonry chimney. (Mobile Home must be
equipped with a spark arrestor.) Maximum depth of Alcove shall be no more than 48 inches (1219mm) with a minimum
height of 84 inches (2133mm) from floor to bottom of ceiling, and the referenced clearances.
8
MANTEL
12" MAX
J
I
B
A
C
D
A
B
7.5
6.5
17.25
(191)
(165)
(438)
6.38
5.38
17.25
(162)
(137)
(438)
5.38
5.38
17.25
(137)
(137)
(438)
NA
NA
17.25
(438)
WARNING
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
• Failure to comply may cause house fire.
7061-197B
United States and Canada (UL and ULC)
Fuel loading door
8 in.
16 in. from glass
35-1/4 in. min.
203mm
(8 in.)
C
D
E
F
6.5
7.0
10.5
(165)
(178)
(267)
6.5
4.5
7.5
(165)
(114)
(191)
6.5
NA
NA
(165)
6.5
NA
NA
(165)
36 in.min.
8 in.
203mm (8 in.)
203mm
(8 in.)
457mm (18 in.)
1143mm (45in.) min.
G
H
I
55
NA
NA
(1397)
55
NA
NA
(1397)
55
26.25
NA
(1397)
(667)
55
NA
12
(1397)
(305)
February 18, 2014
1175mm
(46.25 in.)
minimum
J
NA
NA
NA
50
(1270)