Possible types of benefit kWh rate power supply
Possible connections and requirements to connect the equipment to
such power supply are illustrated in the figures below:
For V1 unit types only (1~)
[6-04]=1
1
L N
1
S1S
2
3
2
L N
1
2
S1S
3
3
L N
1
S1S
2
3
6
3
L N
X1M
RSQ/
RRQ
*
*
1
Benefit kWh rate power supply box
2
Receiver controlling the signal of the electricity company
3
Benefit kWh rate power supply
4
Voltage free contact to indoor unit
5
Normal kWh rate power supply
6
Fuse (field supply)
EKHBRD011~016AAV1+Y1
Indoor unit for air to water heat pump system
4PW54465-1A
[6-04]=2
1
L N
1
S1S
2
4
3
2
L N
1
2
S1S
4
3
3
L N
1
S1S
2
4
3
L N
6
4
5
7 8
X3M
8 9
X2M
KHBRD
*
7 8
9 10
X2M
For Y1 unit types only (3~)
[6-04]=1
1
L1
L2L3
1
2
3
2
L1
L2L3
1
4
2
3
3
L1
L2L3
1
4
2
3
4
6
3
RSQ/
RRQ
*
*
1
Benefit kWh rate power supply box
2
Receiver controlling the signal of the electricity company
3
Benefit kWh rate power supply
4
Voltage free contact to indoor unit
5
Normal kWh rate power supply
6
Fuse (field supply)
In case of benefit kWh rate power supply installation,
remove the wiring bridges on X2M before installing the
normal kWh rate power supply.
When the outdoor unit is connected to a benefit kWh rate power
supply, the voltage free contact of the receiver controlling the benefit
kWh rate signal of the electricity company must be connected to
clamps 7 and 8 of X3M (as illustrated in the figure above).
When parameter [6-04]=1 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will open and
the unit will go in forced off mode
When parameter [6-04]=2 at the moment that the benefit kWh rate
signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
(1) When the signal is released again, the voltage free contact will close and the unit
will restart operation. It is therefore important to leave the auto restart function
enabled. Refer to field setting "[8] Option setup, [8-01]" in the chapter
settings" on page
(2) When the signal is released again, the voltage free contact will open and the unit
will restart operation. It is therefore important to leave the auto restart function
enabled. Refer to field setting "[8] Option setup, [8-01]" in the chapter
settings" on page
[6-04]=2
1
N
1
S1S
2
4
3
2
N
1
S1S
2
4
3
3
N
1
S1S
2
4
3
6
4
L1 L2
L3
N X1M
X1M
7 8
X3M
KHBRD
*
7 8
(1)
.
(2)
.
17.
17.
L1
L2L3
N
S1S
4
L1
L2L3
N
S1S
4
L1
L2L3
N
S1S
4
L N
5
8 9
X2M
9 10
X2M
"Field
"Field
Installation manual