Bosch DS484Q Installation Instructions Manual page 8

Quad beam photoelectric detectors
Table of Contents

Advertisement

DS484Q/DS486Q | Installation Instructions | 3.0
3.0 Wiring
Apply power only after all connections are
made and inspected.
Install these detectors according to the
National Electrical Code, NFPA-70.
Table 7 is based on one set (transmitter and receiver)
connected to the same wire run from the power source.
When installing two or more sets on one wire run,
calculate the maximum length by dividing the
maximum listed wire length by the number of sets
installed.
Connect the transmitters and receivers to a UL Listed
power supply or control panel capable of providing
standby power for at least 4 hours.
Test this system at least once a week to ensure proper
operation.
Table 3:
Wire Length / AWG Chart
Wire
Maximum Distance [m (ft)]
Gauge
DS484Q
2
[mm
12 VDC
(AWG)]
0.8
90
(22)
(295)
1.06
180
(19)
(591)
1.37
330
(17)
(1083)
1.8
590
(14)
(1936)
8
DS486Q
24VDC
12VDC
24VDC
850
80
(2789)
(295)
(2395)
1670
150
(5479)
(492)
(4659)
3020
280
(9908)
(919)
(8465)
5370
500
(17618)
(1640)
(14993)
Wiring
Figure 10: Transmitter, Terminal Block Wiring
1 - Power (non-polarized), 10.5 VDC to 28.0 VDC
2 - Tamper Output (1b), 30 VDC 0.1 A
3 - Synchronized wiring
Figure 11: Receiver, Terminal Block Wiring
730
1420
2580
4570
1 - Power (non-polarized), 10.5 VDC to 28.0 VDC
2 - Alarm Output (1c), 30 VDC 0.2 A
3 - EDC Output (1b), 30 VDC 0.2 A
4 - Tamper Output (1b), 30 VDC 0.1 A
Bosch Security Systems, Inc. | 7/05 | 4998138530F
+
1
-
COM
2
NC
3
+
1
-
COM
NC
2
NO
EDC
3
NC
TAMPER
4
NC

Hide quick links: