NEC SECTION 210-20 (A)
Table 310-16. Allowable Ampacities of Insulated Conductors Rated O Through 2000 Volts, 140°F Trough
194°F (60°C Trough 90°C) Not More than Three Current-Carrying Conductors in Raceway, Cable, or Earth
(Directly Buried), Based on Ambient Temperature of 86°F (30°C).
Size
140°F (60°C)
Types
TW, UF
AWG
or
kcmil
18
---
---
16
14
20
12
25
30
10
8
40
6
55
4
70
3
85
95
2
1
110
1/0
125
2/0
145
165
3/0
4/0
195
250
215
300
240
260
350
400
280
500
320
600
355
385
700
750
400
800
410
900
435
1000
455
495
1250
1500
520
1750
545
560
2000
Ambient
Temperature
70 – 77°F (21 – 25°C)
79 – 86°F (26 - 30°C)
88 – 95°F (31 - 35°C)
97 – 104°F (36 - 40°C)
106 – 113°F (41 - 45°C)
115 – 122°F (46 - 50°C)
124 – 131°F (51 - 55°C)
Modifications reserved
OPM_SGS_ISG_M40_M50_2US_V021.doc
Temperature Rating of Conductor (See table 310-13)
167°F (75°C)
194°F (90°C)
Types
Types
FEPW, RH, RHW,
TBS, SA, SIS, FEP,
THHW, THW,
FEPB, MI, RHH,
THWN, XHHW,
RHW-2, THHN,
USE, ZW
THHW, THW-2,
THWN-2, USE-2,
XHH, XHHW,
XHHW-2,ZW-2
COPPER
---
---
20
25
35
50
65
85
100
110
115
130
130
150
150
170
175
195
200
225
230
260
255
290
285
320
310
350
335
380
380
430
420
475
460
520
475
535
490
555
520
585
545
615
590
665
625
705
650
735
665
750
For ambient temperatures other than 86°F (30°C), multiply the allowable ampacities shown above by the
1.08
1.05
1.00
1.00
0.91
0.94
0.82
0.88
0.71
0.82
0.58
0.75
0.41
0.67
140°F (60°C)
Types
TW, UF
ALUMINIUM or COPPER-CLAD ALUMINIUM
14
---
18
---
25
---
30
20
40
25
55
30
75
40
95
55
65
75
85
100
115
130
150
170
190
210
225
260
285
310
320
330
355
375
405
435
455
470
CORRECTION FACTORS
appropriate factor below
1.04
1.08
1.00
1.00
0.96
0.91
0.91
0.82
0.87
0.71
0.82
0.58
0.76
0.41
167°F (75°C)
194°F (90°C)
Types
Types
RH, RHW,
TBS, SA, SIS,
THHW,
THHN, THHW,
THW, THWN,
THW-2,
XHHW, USE
THWN-2, RHH,
RHW-2, USE-2,
XHH, XHHW,
XHHW-2,
ZW-2
---
---
---
---
---
---
20
25
30
35
40
45
50
60
65
75
75
85
90
100
100
115
120
135
135
150
155
175
180
205
205
230
230
255
250
280
270
305
310
350
340
385
375
420
385
435
395
450
425
480
445
500
485
545
520
585
545
615
560
630
1.05
1.04
1.00
1.00
0.94
0.96
0.88
0.91
0.82
0.87
0.75
0.82
0.67
0.76
Page 21/41