Heatilator ADI-ZC-FB Installer's Manual page 9

Heatilator vented gas fireplace heater
Table of Contents

Advertisement

Figure 3.
WARNING: THE EXHAUST VENT PIPE MUST
!
ONLY BE CONNECTED TO THE EXHAUST
STARTING COLLAR OF THE UNIT AND THE
CENTER COLLAR OF THE TERMINATION CAP.
A 3 FOOT SECTION OF STAINLESS STEEL
!
FLEXIBLE LINER MUST BE ATTACHED
DIRECTLY TO THE EXHAUST COLLAR ON
COLLAR SLIDE PLATE.
TERMINATION
CAP
SQUARE FLASHIN
INLET AIR COLLAR
EXHAUST COLLAR
EXHAUST
VENT PIPE
V= 14 FT. MINIMUM
50FT. MAXIMUM
3 INCH COLLAR
(Factory installed to
stainless steel section)
WARNING: DO NOT
BLOCK PIPE END WITH
INSULATION OR ANY OTHER
SEALING MATERIAL
STAINLESS STEEL
PIPE - 3 FT. MIN.
REQUIRED (INCLUDED)
SEAL DAMPER
AREA
INLET AIR
VENT PIPE
COLLAR ATTACHMENT
BRACKET
Heatilator • ADI-ZC-FB • 2032-900 Rev. E • 8/05
This option shows both exhaust and inlet
air vent pipes attached to the adaptor.
G
THE INLET AIR PIPE MUST ONLY BE
!
CONNECTED TO THE INLET AIR COLLAR OF
THE UNIT AND EITHER ATTACHED TO THE
INLET AIR COLLAR OF THE TERMINATION CAP
OR TERMINATED IN THE CHIMNEY.
11