Heatilator ADI-ZC-FB Installer's Manual page 8

Heatilator vented gas fireplace heater
Table of Contents

Advertisement

Attach the flashing and termination cap
to the top of the flexible vent pipe and set
the cap in place. See Figures 3 and 4.
CAUTION: TO AVOID DOWNDRAFTS
AND/OR COLD AIR PROBLEMS, IT IS
RECOMMENDED TO SEAL OFF THE
AREA BETWEEN THE TERMINATION
CAP AND THE TOP OF THE SOLID-
FUEL CHIMNEY OPENING INTO
WHICH THE VENT CAP HAS BEEN IN-
STALLED.
WHEN USING THE LINK-DV4-30 VENT
SYSTEM, IT IS REQUIRED TO SEAL
AROUND THE FLEXIBLE VENT PIPES
IN THE DAMPER AREA. SEE FIGURE
3. USE FIBERGLASS INSULATION OR
OTHER SUITABLE NON-COMBUSTI-
BLE MATERIAL.
WARNING: MAJOR U.S.
BUILDING CODES SPECIFY
!
MINIMUM CHIMNEY AND/OR
VENT HEIGHT ABOVE THE ROOF
TOP. THESE MINIMUM HEIGHTS
ARE NECESSARY IN THE INTEREST
OF SAFETY. SEE THE FOLLOWING
DIAGRAM FOR MINIMUM HEIGHTS,
PROVIDED THE TERMINATION CAP
IS AT LEAST 2-FEET FROM A VER-
TICAL WALL AND 2-FEET BELOW
A HORIZONTAL OVERHANG.
NOTE: This also pertains to vertical vent
systems installed on the outside of the
building.
10
2 FT.
MIN.
TERMINATION CAP
Roof Pitch
flat to 6/12
over 6/12 to 7/12
over 7/12 to 8/12
over 8/12 to 9/12
over 9/12 to 10/12
over 10/12 to 11/12
over 11/12 to 12/12
over 12/12 to 14/12
over 14/12 to 16/12
over 16/12 to 18/12
over 18/12 to 20/12
over 20/12 to 21/12
Figure 2. Minimum Height from Roof to Lowest
Discharge Opening
Heatilator • ADI-ZC-FB • 2032-900 Rev. E • 8/05
HORIZONTAL OVERHANG
VERTICAL WALL
2 FT. MIN.
LOWEST
DISCHARGE
OPENING
X
12
ROOF PITCH IS X/ 12
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
H (min.) ft.
1.0
1.25
1.5
2.0
2.5
3.25
4.0
5.0
6.0
7.0
7.5
8.0