Venting Connection - Viessmann Vitorond 100 VR1 Series Installation And Service Instructions Manual

Oil-fired boiler heating input 91 to 140 mbh 27 to 41 kw
Table of Contents

Advertisement

Vitorond 100, VR1-22 to -33 Installation and Service

Venting Connection

Vitorond 100
The vent system must comply with all applicable local
and/or national codes.
If installing boiler with a side wall vent system, ensure
all manufacturer's requirements are met.
Venting codes
For oil-fired boilers install venting system in accordance
with all applicable local codes:. In the absence of local
codes, follow national codes
Local codes or CSA B139-00 in Canada,
g
or
NFPA-31 in the U.S.
g
Building codes
Masonry or concrete or metal chimneys (smokestacks)
shall be constructed according to the requirements of
the province/state building code or, in the absence of
such regulations, in accordance with:
CSA Standard CAN/CSA-A405
g
(National Building Code of Canada) in Canada, or
NFPA 211 (Standard for Chimneys, Fireplaces, Vents,
g
and Solid Fuel-Burning Appliances) in the US. Metal
chimneys also shall meet the requirements of Chapter
4 of NFPA 211.
In Canada, factory built chimneys shall:
Conform to ULC Standards
g
CAN/ULC-S629 for 1202° F (650° C),
CAN/ULC-S604 for Type A, or
CAN/ULC-S609 for Type L chimneys,
Be certified and installed in accordance with the
g
manufacturer's certified instructions, and
Be provided with a clean-out opening that is equipped
g
with a tight-fitting removable cap, and constructed so
that no air can enter the clean-out facility when the cap
is in place.
In the U.S., factory built chimneys shall:
Meet the requirements of NFPA, and
g
Be listed, installed and used in accordance with their
g
listings and manufacturer's instructions.
WARNING
Improper sizing, maintenance, termination of vent or
chimney can cause flue gases to enter living space.
Any blockage of vent or chimney by birds' nests, ice,
snow, debris, or other materials can cause flue gases
to enter living space. Flue gases entering living space
can cause carbon monoxide poisoning which can
result in severe personal injury or loss of life.
General
The heating contractor shall ensure all of the following
requirements are met:
The vent system shall ensure that no hazard is created
g
by the products of combustion.
Provision shall be made to vent the products of
g
combustion safely to outside the building, and
such venting shall not pass through or be installed
in return air, supply air, ventilating, or combustion air
ducts or shafts.
Sufficient air for combustion of the oil and ventilation
g
of the appliance shall be supplied to the space wherein
the appliance is located (see section entitled
Combustion Air Supply).
The house and its mechanical systems shall be
g
inspected to determine if operation of exhaust devices
could lead to levels of depressurization of the house
that would adversely affect the operation of the oil-
burning appliance and its venting system. If such is the
case, the building owner shall be informed of the
situation in writing.
The chimney shall be inspected to ensure that the
g
material construction, condition, and size are suitable
for the application.
This boiler/burner combination shall not be connected
g
to an unlined chimney. Such chimneys shall be lined
in accordance with the applicable codes and standards.
The chimney shall be capable of exhausting the
g
products of combustion and of producing a draft
not less than that recommended by the manufacturer
of the appliance connected thereto, during the mildest
weather conditions under which the appliance is
expected to operate.
During cold weather testing, excess flow performance
shall be demonstrated to ensure that flow is adequate
in warmer weather.
An oil burning appliance that depends on natural
g
chimney draft shall be connected to an individual
chimney vent used for no other appliance, except
as permitted by the applicable codes and standards.
The vent connector of this boiler must not be
g
connected into any portion of mechanical draft
systems operating under positive pressure.
A chimney flue shall extend at least 3 ft (1 m) above
g
the highest point at which the chimney comes in
contact with the roof, and not less than 2 ft (0.6 m)
above the highest roof surface or structure within
10 ft. (3 m) of the chimney on a horizontal plane
perpendicular to the chimney. Not more than 8"
(200 mm) of chimney flue above the top of the
chimney cap shall be considered in computing height.
Down draft and condensation problems must be
g
corrected.
WARNING
Never operate the boiler/burner without an installed
venting system which safely vents all products of
combustion to the outdoors. The vent system must
comply with all applicable local and/or national codes.
Connections
15