Set-up

Product Delivery

Unpacking Instructions

WARNING
To avoid injury and to facilitate boiler maneuvering,
it is strongly recommended that Viessmann carrying
handles (Part No. 7189 602) be used. The carrying
handles allow easy removal of boiler from skid and
enables easy transportation to permanent location,
while reducing the risk of boiler panel damage due to
improper lifting or maneuvering techniques. The
carrying handles are designed to prevent boiler
slippage onto hand when carrying up/down inclines.
Legend
A Casting
B 1" pipe, x2
C Rear wooden block
D Front wooden block
12
Vitorond 100, VR1-22 to -33 Installation and Service
Vitorond boilers size VR1-22 to VR1-33 are shipped in
a crate with separate boiler jacketry.
Product delivery
Ensure each of the following has been
delivered:
H Crate with boiler A
H Carton with burner (shipped separately)
H Carton with standard installation equipment
CAUTION
Do not lift or position boiler alone.
Do not lift by or push against panels.
Do not bump boiler panels against floor.
Do not drop boiler.
CAUTION
To avoid injury to hands, place wooden block under
pipes in front of skid.
If carrying handles are not available, follow the steps
below.
1. Remove top and sides of crate.
To avoid damage during lifting, carefully remove
front panel by lifting panel up and out.
2. Place wooden block 12" from rear of skid.
3. Insert 1" Ø Schedule 40 pipes through openings in
casting legs. Ends of pipes should be centered on
wooden block behind skid.
4. Lift boiler using pipes until clear from skid. Remove
skid from beneath boiler.
5. Lower boiler until pipes rest on front block.
6. To remove rear block, lift (by casting - not jacket)
to tilt unit forward.
To remove front block, lift (by casting - not jacket)
to tilt unit backward.
7. Remove pipes. Reinstall front boiler panel once boiler
is in final position.