Burner Installation; Burner Information - Viessmann Vitorond 100 VR1 Series Installation And Service Instructions Manual

Oil-fired boiler heating input 91 to 140 mbh 27 to 41 kw
Table of Contents

Advertisement

Burner - Beckett

Burner Installation

Burner Information

24
Vitorond 100, VR1-22 to -33 Installation and Service
Refer to instructions supplied with
the Beckett burner.
Observe all instructions supplied with the burner.
Fuel
This boiler is for use with the Beckett #2 fuel oil burner
supplied by Viessmann only. Use only the fuel stated on
the rating plate of the burner.
WARNING
DO NOT USE GASOLINE
CRANKCASE DRAININGS OR ANY
OIL CONTAINING GASOLINE.
Oil nozzle
The Beckett burner for the VR1-63 boiler is shipped with
factory setting and oil nozzle installed. For VR1-50
boiler, replace installed nozzle with nozzle packaged with
burner. For Beckett burner specifications see table on
page 47.
Burner calibration
Ensure that the combustion results of the oil-fired burner
mounted on this boiler are verified after start-up.
If adjustments are necessary, always verify results with
a calibrated flue gas analyzer.
For Beckett burner specifications see table on page 47.
IMPORTANT
This burner is shipped with the oil pump set to operate
on a single line system. To operate on a two-line system,
the bypass plug must be installed. The burner is shipped
configured for use in single line applications. No changes
to the oil pump are required for use in single line
applications.