Obvius A89WS Installation And Operation Manual page 29

Obvius weather station installation and operation manual
Table of Contents

Advertisement

Mode setting options (see above for value details)
64
40065
UINT16
65
40066
UINT16
66
40067
UINT16
67
40068
UINT16
68
40069
UINT16
69
40070
UINT16
70
40071
UINT16
71
40072
UINT16
73
40074
UINT16
74
40075
UINT16
75
40076
UINT16
System settings and information
1002
41003
UINT16
1003
41004
UINT16
1004
41005
UINT16
1005
41006
UINT16
1006
41007
UINT16
1011
41012
UINT32
1012
41013
UINT32
1013
41014
UINT16
1014
41015
UINT16
1015
41016
UINT32
1016
41017
UINT32
1017
41018
UINT16
1018
41019
UINT16
1019
41020
UINT16
1020
41021
UINT16
1024
41025
UINT8
1025
41026
UINT16
1026
41027
INT16
1027
41028
UINT16
1028
41029
UINT16
Modbus function 0x11 Slave ID response will report the following:
"Obvius, A8332-8F2D, IO Module, 8-Flex, 2-DO", id=48
Page 29
input 1 mode (NV/r/w)
input 2 mode (NV/r/w)
input 3 mode (NV/r/w)
input 4 mode (NV/r/w)
input 5 mode (NV/r/w)
input 6 mode (NV/r/w)
input 7 mode (NV/r/w)
input 8 mode (NV/r/w)
input broken wire alarm bitmap. (resistance, current modes only) Resistive mode: bit
set when resistance is off-scale-high. 4-20mA mode: bit is set when current is below
4mA.
relay output 1 (r/w) 0=open, 1=closed, defaults to open on power-up. r/w allowed when
register 41030 = 0.
relay output 2 (r/w) 0=open, 1=closed
serial number bytes 1,2
serial number bytes 3,4
serial number bytes 5,6
firmware version (major)
firmware version (minor)
uptime MSW number of seconds since IO module booted.
uptime LSW
hardware version (major) for example: 8332
hardware version (minor) MSB = pcb rev, LSB = part rev. value 1=Rev_A, 2=Rev_B,
etc.
hardware Date of Manufacture (MSW)
hardware Date of Manufacture (LSW) time, UTC, unix epoch, seconds past 1970.
RS485 Stats: Good RX (all packets received)
RS485 Stats: Total TX
RS485 Stats: TX failed
clear min/max/ave (r/w) read returns 0, write any value to clear min/max/ave for all
channels.
reason for reboot. 0x01=POR, 0x02=EXTR 0x04=WDTR
0x08=BODR,0x8000=WDTOF
power supply voltage monitor. scale: x100, volts
pcb temperature monitor. scale: x100, degrees F.
5V internal power supply voltage monitor. scale: x100, volts
RS485 baud rate. 2=9600, 3=19200.