Channel 4: A89WS-TC1,TC2: Cell Temperature

Configure the following options
Sensor Name: "Cell Temperature"
Input Mode: "Resistance"
Sensor Make and Model:
"A89WS-TC1 (Veris TRASPC01331)"
Curve Scale: "Veris 10K Type 2"
Engineering Units: "Degrees F"
Note: the option for "Sensor make and model" is for reference
information only. This field is intended to store information
about the physical sensor to assist in record keeping for
identification of the attached sensor.
The Curve Scale option has a provision for converting 10K Type 2 to either Degreees F or C. You may select either
conversion depending on your project needs. Be sure to set the Engineering Units field to match the unit of measure for
your conversion.

Channel 5: A89WS-AN1,AN2: Anemometer / wind speed

Configure the following options
Sensor Name: "Wind Speed"
Input Mode: "Current 4-20mA"
Sensor Make and Model:
"A89WS-AN1 (NovaLynx 200-WS-02)"
Sensor Minimum Range: "0"
Sensor Maximum Range: "100"
Engineering Units: "MPH"
Note: the option for "Sensor make and model" is for reference
information only. This field is intended to store information
about the physical sensor to assist in record keeping for
identification of the attached sensor.
Page 25
Draft Copy
A89WS Weather Station (gen 3)