8 Troubleshooting
19
Alarm code
The RUN LED flickers and "ALARM" is displayed on the remote control switch.
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB1.
-
This alarm code is displayed when the following conditions occurs three times in 30 minutes. Indoor fan rotates less
than 70 rpm for 5 seconds during operation.
When the cause is checked by means of this flow chart, confirm that fan speed setting is Hi
241
SMGB0064 rev.0 - 08/2011

Activation of the protection device for the indoor fan motor (RCI, RCIM)