8 Troubleshooting
4 Turn ON the power supply.
After finishing the checking, turn OFF the power supply again and reconnect the connectors according to the previous
situation before the checking.
N O T E
If this indication continues and the alarm code J1is not displayed, this means that each one of indoor unit is
not connected to the remote control switch.
Check the wiring between the remote control switch and the indoor unit.
In this troubleshooting procedure, checking of the following parts of the PCB is not available.
-
PCB in Indoor Unit: Relay circuit, DIP switch, option circuit, fan circuit, protection circuit.
-
PCB in Outdoor Unit: Relay circuit, DIP switch, option circuit.
If this troubleshooting is performed in the system by means of the central station, the indication of the central
station may change during this procedure. However, this is not abnormal.
After this troubleshooting, the memory of the abnormal operation occurrence counter, which was described
before, will be deleted.