10 Servicing

 
Opening electrical box (P-Mounting Plate)
1 Remove the service cover following
2 Remove six (6) screws which fix the electrical box and open the P plate turning counter clockwise approximately 90°.
Check that the LED201 (red) on the inverter PCB (PCB2) is OFF when opening P-mounting plate.
1. Upper cover.
2. P Plate.
3. Screw.
4. Two (2) screws.
5. Electrical box (view from top).
6. P-Mounting plate.
7. Opening direction of P-Mounting Plate.
D A N G E R
DO NOT touch electrical components while the LED201 (Red) is ON to avoid electrical shock. Wait until the
LED turns off.

 
Removing reversing valve coil
1 Remove the service cover according to the item
2 Check to ensure the LED201 (Red) of the inverter PCB (PCB2) is OFF.
N O T E
DO NOT touch electrical components while the LED201 (Red) is ON to avoid electrical shock. Wait until the
LED turns off.