7 Test Run
Check to ensure that the main source has been ON for more than 12 hours to warm the compressor oil by the
oil heater.
Check to ensure the operating temperature:
-
Cooling operation:
Š Indoor DB 21.5 ºC and above,
Š Indoor WB 16 ºC and above,
Š Outdoor DB 0 ºC and above
-
Heating operation:
Š Indoor DB 27 ºC and below.
N O T E
Stoppage of compressor operation.
The compressor is NOT available within 4 hours after turning ON the power supply.
(Stoppage code: d1-22) If the compressor should be within 4 hours, turn ON the power and wait for more than
30 seconds. Press PSW1 and PSW3 on the outdoor PCB simultaneously for more than 3 seconds. The forced
thermo-OFF function (d1-22) is cancelled and the compressor operation is available.
175
SMGB0064 rev.0 - 08/2011