7 Test Run
•
Check to ensure that the main source has been ON for more than 12 hours to warm the compressor oil by the
oil heater.
•
Check to ensure the operating temperature:
-
Cooling operation:
Indoor DB 21.5 ºC and above,
Indoor WB 16 ºC and above,
Outdoor DB 0 ºC and above
-
Heating operation:
Indoor DB 27 ºC and below.
N O T E
•
Stoppage of compressor operation.
•
The compressor is NOT available within 4 hours after turning ON the power supply.
•
(Stoppage code: d1-22) If the compressor should be within 4 hours, turn ON the power and wait for more than
30 seconds. Press PSW1 and PSW3 on the outdoor PCB simultaneously for more than 3 seconds. The forced
thermo-OFF function (d1-22) is cancelled and the compressor operation is available.