Hitachi RAS-(3-6)HVRNM2E Service Manual page 332

Utopia dc-inverter ivx/(2/2.5)hp/es series air conditioner
Table of Contents

Advertisement

8 Troubleshooting
Model for ES
RAS-(2/2.5)HVRN2
RAS-3HVRNS2
RAS-4H(V)RNS2E
RAS-5/6H(V)RNS2E
RAS-(8/10)HRNSE
N O T E
-
(*) Values are shown for referential purpose. While actual values may vary depending on the type of the
tester; any tester can be used to determine any short-circuit or breakage based on ∞ or several Ω/several
kΩ or 0Ω
Other parts
Part name
Drain up motor
Solenoid gas for gas bypass
Reversing valve
Expansion valve
Compressor motor
322
SMGB0064 rev.0 - 08/2011
Motor model
Red-Black
FPD10U4OS-902 or
13.5 ~ 14.4
DAJ12-55V71
SIC-68FV-D851-7
1 MΩ or greater
SIC-81FV-D8138-1
1 MΩ or greater
SIC-81FW-D81382
1 MΩ or greater
Unit models
RCI-1.0-FSN3E
RCIM-1.5-.5FSN2
RPI-2.0-6.0FSN3E
RCD.1.0~6.0FSN2
RAS-(4-6)HVRNS2E
RAS-(8/10)HRNSE
RAS-(2/2.5)HVRN2
RAS-3HVRNS2
RAS-(4/5)HVRNS2E
RAS-6HVRNS2E
RAS-(8/10)HRNSE
Wire color for checking (normal value)
White-Black
Yellow-Black
1 MΩ or greater
225~226 kΩ
42 ~ 78 kΩ
166 ~ 312 kΩ
42 ~ 78 kΩ
166 ~ 312 kΩ
42 ~ 78 kΩ
168 ~ 312 kΩ
Model code
ADP-1403
KJV-1004
105-52-52 (50Hz)
105-52-51 (60Hz)
STF-01AJ502D1 (50Hz)
STF-01AI511A1 (60Hz)
UKV-U029E
EU1114D6
EU1318D1
E306A4D-27A2
E406AHD-36A2
E655DHD-65D2
Blue-Black
1 MΩ or greater
1 MΩ or greater
1 MΩ or greater
1 MΩ or greater
Resistance (Ω)
139.00
at 21 ºC
347.00
at 20 ºC
1540.00
at 20 ºC
1250.00
at 20 ºC
1435.00
at 20 ºC
1358.00
at 20 ºC
46.00
at 20 ºC
1.089
at 75 ºC
0.879
at 75 ºC
0.295
at 75 ºC
0.246
at 75 ºC
0.839
at 20 ºC