Vent And Combustion Air Hoods (Dcg Models); Vent And Combustion Air Hoods - York D1CE Installation Instructions Manual

Electric / electric & gas / electric single package air conditioners
Table of Contents

Advertisement

530.18-N11Y

VENT AND COMBUSTION AIR HOODS

(DCG Models)
Two vent hoods and a combustion air hood (with screens) are
shipped attached to the blower housing in the blower
compartment. These hoods must be installed to assure proper
unit function. All hoods must be fastened to the outside of the
gas heat access panel with the screws provided in the bag also
attached to the blower housing.
The screen for the combustion air intake hood is secured to the
inside of the access panel opening with four fasteners and the
screws used for mounting the hood to the panel. The top flange
of this hood slips in under the top of the access panel opening
when installing. Refer to Figure 8.
Each vent hood is installed by inserting the top flange of the
hood into the slotted opening in the access panel and securing
in place.
FIG. 8 - VENT AND COMBUSTION AIR HOODS
8
OPTIONAL ECONOMIZER/MOTORIZED DAMPER
RAIN HOOD
The instruction for the optional economizer/motorized damper
rain hood can be found in form 44-320-2. Use these instructions
when field assembling an economizer rain hood onto a unit.
The outdoor and return air dampers, the damper actuator, the
damper linkage, the outdoor and return air divider baffles, and
all the control sensors are factory mounted as part of the
"Factory installed" economizer option.
ENTHALPY SET POINT ADJUSTMENT
Remove the economizer access panel from the unit to check
the following adjustments. Loosen but do not remove the two
panel latches.
CAUTION: Extreme care must be exercised in turning both the
setpoint and minimum position adjusting screws to
prevent twisting them off.
1. The enthalpy set point may now be set by selecting the
desired setpoint shown in Figure 9. Adjust as follows:
For a single enthalpy operation, carefully turn the set
point adjusting screw to the "A", "B", "C" or "D" setting
corresponding to the lettered curve.
For a dual enthalpy operation, carefully turn the set point
adjusting screw fully clockwise past the "D" setting.
2. To check that the damper blades move smoothly without
binding, carefully turn the minimum position adjusting
screw fully clockwise and then energize and de-energize
terminals "R" to "G". With terminals "R" to "G" energized,
turn the minimum position screw counterclockwise until the
desired minimum position has been attained.
3. Replace the economizer access panel. Reposition the two
latches horizontally and retighten the screws.
POWER EXHAUST/BAROMETRIC RELIEF
DAMPER AND RAIN HOOD OPTION
The instructions for the power exhaust/barometric relief
damper and rain hood can be found in form 44-320-10. The
exhaust fan, all supporting brackets, angles, and the wiring are
factory installed as part of the power exhaust option.
All of the components, including the dampers, hardware, and
mounting instructions are shipped in a single package external
from the unit. The hood must be field assembled and installed.
Power exhaust is not available as a field installed option.
Unitary Products Group

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D1cg300

Table of Contents