Electric characteristics

7. Electric Characteristics
Model
DCT 100HSPi
DCT 140HSPi
DCT 170HSPi
Symbols:
MCA: Min. Circuit Amps(A)
MFA: Max. Fuse Amps(See note 5)
KW: Fan Motor Rated Output(KW)
FLA: Full Load Amps
IFM: Indoor Fan Motor
Note:
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
listed range limits;
2. Maximum allowable voltage unbalance between phases is 2%;
3. MCA/MFA
MCA=1.25*FLA
MFA<=4*FLA
(Next lower standard fuse rating Min. 15A);
3. Select wire size based on the MCA;
5. Instead of fuse, use circuit breaker.
DCT 100HSPi, DCT 140HSPi, DCT 170HSPi
Units
Hz
Voltage
50
380
50
380
50
380
Min. Voltage
Max. Voltage
342
418
342
418
342
418
Power supply
IFM
MCA
MFA KW
FLA
0.9125
15
80
2.8125
15
350
2,25
2.8125
15
350 2,25