Ensure the vent is located where it will not be exposed to prevailing winds.
In all roof venting applications, exhaust discharge must point away from the pitch of the roof.
To prevent water leakage, install adequate roof flashing where the pipe enters the roof.
Do not locate vent over public walkways, driveways, or parking lots. Condensate could drip and freeze, resulting in a slip
hazard or damage to vehicles and machinery.
Due to potential moisture build-up, sidewall venting may not be the preferred venting option. To save time and cost, carefully
consider venting installation and location.
Horizontal lengths of exhaust vent must slope back towards the water heater not less than ¼" per foot to allow condensate to
drain from the vent pipe.
The exhaust vent must terminate where vapors cannot make accidental contact with people or pets, or damage shrubs or
plants.
In vacant chimney applications, install and seal a rain cap over existing chimney openings.
All piping must be fully supported. Use pipe hangers at a minimum of 4 foot intervals to prevent sagging of the pipe where
condensate may form.
Do not use the water heater to support any piping.
Figure 5 – Vent Termination Detail
A
Clearance above grade, veranda, porch, deck, or balcony
B
Clearance to window or door that may be opened
C
Clearance to permanently closed window
Vertical clearance to ventilated soffit located above the
D
terminal within a horizontal distance of 2 feet from the center
E
Clearance to unventilated soffit
F
Clearance to outside corner
G
Clearance to inside corner
Clearance to each side of center line extended above meter
H
/ regulator assembly
I
Clearance to service regulator vent outlet
Clearance to non-mechanical air supply inlet to building or
J
the combustion air inlet to any other appliance
K
Clearance to a mechanical air supply inlet
L
Clearance above paved sidewalk or driveway located
M
Clearance under veranda, porch, deck, or balcony
Table 8 – Vent Termination Clearances - *NOTE: For clearances not specified in ANSI Z223.1/NFPA 54 or CAN/CSA-B 149.1,
please use clearances in accordance with local installation codes and the requirements of the gas supplier.
DESCRIPTION
line of the terminal
US
1 foot
1 foot
*
*
*
*
*
*
*
1 foot
3 feet above if within 10 feet
horizontally
*
*
CANADA
1 foot
3 feet
*
*
*
*
*
3 feet with a height 15 feet
above meter / regulator assembly
3 feet
3 feet
6 feet
7 feet
1 foot
WHL-004 REV. 12.17.14
17