9-17. Test Run Procedure

Recheck the items to check
(See 9-18)
before the test run.
Check the combination (wiring) of
(See 9-21-1)
indoor and outdoor units.
YES
Is system "single-type"?
NO
NO
Is outdoor unit multiple?
Turn ON the
indoor and
outdoor power.
YES
Automatic
Address
(See 9-21-2) How to Set the
Outdoor Unit System Address
Set the outdoor unit system
address.
(See 9-21-1) How to Set
Automatic Address
Set the automatic address
setting from outside unit or
remote controller.
(*) Indicate (mark) the combination number. (See 9-21-3, 4)
Turn ON the indoor and outdoor power.
Automatic Address
Set the remote controller to
(See 9-19)
"test run".
(See 9-20)
NO
Refer to "Table of
Can
Self-Diagnostic
operation be
Functions" to check
started?
the system.
In addition, refer to
Item 9-21 and correct
any items that need to
YES
be corrected.
Return the remote controller
Note: Check the indoor-
to normal control.
side drainage.
(*) Required for
simultaneous-operation
multi systems and for
group control.
Fig. 9-14

9-18. Items to Check Before the Test Run

(1) Turn the remote power switch ON at least 12 hours in
advance in order to energize the crank case heater.
(2) Fully open the closed valves on the liquid-tube and gas-
tube sides.

9-19. Test Run Using the Remote Controller

(1) Press and hold the remote controller
button for 4
seconds or longer. Then press the
button.
"TEST" appears in the LCD display during the test run.
Temperature control is not possible when test run mode
is engaged.
(This mode places a large load on the devices. Use it
only when performing the test run.)
(2) Use either Heating or Cooling mode to perform the test
run.
Note: The outdoor unit will not operate for approximately 3
minutes after the power is turned ON or after it stops
operating.
(3) If normal operation is not possible, a code appears on the
remote controller LCD display.
Refer to "9-20. Table of Self-Diagnostic Functions and
Corrections" on the next page, and correct the problem.
(4) After the test run is completed, press the
button again.
Check that "TEST" disappears from the LCD display.
(This remote controller includes a function that cancels test
run mode after a 60-minute timer has elapsed, in order to
prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the
compressors for a minimum of 10 minutes (in order to
check for open phase).
* When performing a test run using a wired remote
controller, operation is possible without attaching the
cassette-type ceiling panel.
("P09" will not be displayed.)
33

9-20. Table of Self-Diagnostic Functions and Corrections (E1 Type)

Cause
Wired remote
Indoor unit
controller
Group connection and simultaneous-operation multi
receiver lamp
display
system
• Remote controller is not connected with indoor unit
Nothing is
Nothing is
correctly.
displayed
displayed.
• Indoor unit power is not ON.
• Automatic address setting has not been completed.
• Inter-unit control wiring is cut or is not connected
E01 displayed
correctly.
• Remote controller is not connected with indoor unit
correctly.
Operation lamp
is blinking.
• Remote controller is not connected with indoor unit
E02 displayed
correctly.
• Remote controller crossover wiring is cut or is not
E14 displayed
connected correctly.
• Indoor-outdoor inter-unit wiring is not connected
E04 displayed
correctly.
• Inter-unit control wiring is cut or is not connected
Standby lamp is
E06 displayed
correctly.
blinking.
E15 displayed
• Indoor unit capacity is too low.
E16 displayed
• Indoor unit capacity is too high.
Operation lamp
• Reversed phase at one of the outdoor units in the group.
• Insuffi cient gas
and Standby
P05 displayed
lamp are blinking
alternately.
• Ceiling panel connector at one of the indoor units in the
Timer lamp and
P09 displayed
group is not connected correctly.
Standby lamp
are blinking
• DC fan trouble at one of the indoor units in the group.
P12 displayed
alternately.
L02
• Indoor-outdoor unit type mismatch.
displayed
Both the
L13
Operation lamp
and Standby
• Remote controller crossover wiring is connected to the
L07 displayed
lamp are blinking
indoor unit, however it is set for individual operation.
together.
L10 displayed
• Check outdoor operation with separate maintenance-use remote controller.
Correction
Connect the remote controller correctly. Turn ON the
indoor unit power.
Check the remote controller and inter-unit control
wiring.
Perform automatic address setting (9-21).
Connect the remote controller correctly.
Check the remote controller crossover wiring.
Perform automatic address setting again.
Connect the wiring correctly.
Refer to 9-21-1. Basic wiring diagram, and make the
correct setting.
Check that the total capacities of the indoor and
outdoor units are appropriate.
Reverse 2 phases of the outdoor unit 3-phase power
and connect them correctly.
Fill up the gas appropriately.
Connect the indoor unit ceiling panel connector
correctly.
Check whether the fan holder is loose.
Check the wiring between the DC fan and the PCB.
Check that the indoor and outdoor unit types are
correct.
Perform automatic address setting (9-21).
34