Caution; Test Run Procedure - Panasonic U-36PE1U6 Technical Data & Service Manual

Table of Contents

Advertisement

U1, K1, T1, F1 Type

6-2. Caution

This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit.
The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings
required for operation were made at the time of shipment.
Only the correct combination of indoor and outdoor units can be used.
This test run manual describes primarily the procedure when using the wired remote controller.

6-3. Test Run Procedure

Recheck the items (see IV-4) to check before the test run.
Check the combination (wiring) of indoor and
outdoor units.
Turn ON the indoor and outdoor power.
Set the remote controller to "test run."
Return the remote controller to normal
control.
NO
Automatic
address?
YES
Has the
NO
test run been
completed?
YES
Fig. 6-3
6-3
(See I-98)
Check the warning code.
(See 6-4)
Refer to "Table of Self-Diagnostic
Functions and Corrections" to
check the system.
Note: Check the indoor-side drainage.
6. Test run