9-21-3. Checking indoor unit addresses
Use the remote controller to check the addresses of the indoor
units. Press and hold the
button and
button for 4
seconds or longer (simple settings mode, "ALL" appears on the
remote controller). Then press the
button and select the
indoor address.
(For the system addresses of the No. 1 outdoor unit, each time the
button is pressed, the address changes as follows: 1-1, 1-2, ...)
The indoor unit fan operates only at the selected indoor unit.
Confirm the indoor unit address. (For the system addresses of
the No. 2 outdoor unit, the displayed addresses are 2-1, 2-2, ...)
Press the
button again to return to the normal remote
controller mode.
Fig. 9-18
9-21-4. Indicating (marking) the indoor and outdoor unit
combination number
Indicate (mark) the number after automatic address setting is
completed.
(1) So that the combination of each indoor unit can be easily
checked when multiple units are installed, ensure that
the indoor and outdoor unit numbers correspond to the
system address number on the outdoor unit control PCB,
and use a magic marker or similar means which cannot
be easily removed to indicate the numbers in an easily
visible location on the indoor units (near the indoor unit
nameplates).
Example: (Outdoor) 1 – (Indoor) 1
(Outdoor) 2 – (Indoor) 1
(2) These numbers will be needed for maintenance. Be sure to
indicate them.

9-22. Automatic Address Setting

9-22-1. Basic wiring diagram
● Link wiring
NOT E
● A terminal plug (black) is attached to each of the outdoor unit
control PCBs. At only one outdoor unit, leave the terminal
plug short-circuit socket on the "Yes" side. At all the other
outdoor units, change the socket (from "Yes" to "No").
● A maximum of 8 indoor units can be connected to 1 remote
controller for group control.
Fig. 9-19
37
9-22-2. Setting outdoor unit system addresses
For the basic wiring diagram (Set the system addresses: 1, 2, 3...)
Outdoor unit control PCB
System address rotary switch
(Set to "0" at time of shipment)
System address rotary switch
System address
10s
20s
DIP switch
ON
ON
1
2
OFF
8 – 10 HP
OC (CN500, BLU)
EMG (CN502, BRN)
63PH (CN027, WHT)
SILENT (CN037, WHT)
FUSE (0.5A, F500)
PUMP DOWN (CN048)
EXCT
(CN030, RED)
TEMINAL (CN205, BLK)
RC P
C2 (CN020, WHT)
(CN039, RED)
C1 (CN021, WHT)
IC002
TS (CN022, RED)
FUSE
(6.3A, F101)
TO (CN023, BLK)
TD (CN024, BLK)
MOV1
(CN300, WHT)
CTL2
MOV2
(CN202, GRN)
(CN301, BLK)
CTL1
LED (D041 EEPROM LED)
(CN203, GRN)
EEPROM
N . P . C H E C K
LED2
TEST (CN033, RED)
(CN046, RED)
LED1
C-CHK (CN035)
R.C.ADD. Rotary switch
A.ADD (CN047)
MODE (CN038)
R.C.ADD. DIP switch
IC001
D115
(Power LED)
Fig. 9-20
System address 10s
System address
System address
digit
1s place
No.
(2P DIP switch)
(Rotary switch)
Both OFF
"0" setting
ON
ON
0 Automatic address
(Setting at shipment = "0")
1
2
OFF
Both OFF
"1" setting
ON
ON
1 (If outdoor unit is No. 1)
1
2
OFF
9-22-3. Checking indoor unit addresses
Use the remote controller to check the addresses of the indoor
units. Press and hold the
button and
button for 4
seconds or longer (simple settings mode, "ALL" appears on the
remote controller). Then press the
button and select the
indoor address.
(For the system addresses of the No. 1 outdoor unit, each time
the button is pressed, the address changes as follows: 1-1, 1-2,
...)
The indoor unit fan operates only at the selected indoor unit.
Confirm the indoor unit address.
Press the
button again to return to the normal remote
controller mode.
Fig. 9-21
9-22-4. Indicating (marking) the indoor and outdoor unit
combination number
Indicate (mark) the number after automatic address setting is
completed.
(1) So that the combination of each indoor unit can be easily
checked when multiple units are installed, ensure that
the indoor and outdoor unit numbers correspond to the
system address number on the outdoor unit control PCB,
and use a magic marker or similar means which cannot
be easily removed to indicate the numbers in an easily
visible location on the indoor units (near the indoor unit
nameplates).
Example: (Outdoor) 1 – (Indoor) 1
(Outdoor) 2 – (Indoor) 1
(2) These numbers will be needed for maintenance. Be sure to
indicate them.
38