Table 3-10 Datacorder Alarm Indications - Carrier 69NT40--541--200 TO 299 Operation And Service

Container refrigeration
Table of Contents

Advertisement

Code No.
TITLE
Recorder Supply Tem-
dAL70
perature Out of Range
Recorder Return Tem-
dAL71
perature Out of Range
USDA Temperatures
dAL72-74
1, 2, 3 Out of Range
Cargo Probe 4 Out of
dAL75
Range
dAL76, 77
Future Expansion
Network Data Point
dAL78-85
1 -- 8 Out of Range
dAL86
RTC Battery Low
dAL87
RTC Failure
DataCORDER
dAL88
EEPROM Failure
dAL89
Flash Memory Error
dAL90
Future Expansion
dAL91
Alarm List Full

Table 3-10 DataCORDER Alarm Indications

To Access: Press ALT. MODE key
The supply recorder sensor reading is outside of the range of --50_C to
70_C (--58_F to +158_F) or, the probe check logic has determined there is
a fault with this sensor.
The P5 Pre-Trip test must be run to inactivate the alarm.
The return recorder sensor reading is outside of the range of --50_C to
70_C (--58_F to +158_F) or, the probe check logic has determined there is
a fault with this sensor.
The P5 Pre-Trip test must be run to inactivate the alarm.
The USDA probe temperature reading is sensed outside of --50 to 70°C
(--58 to 158°F) range.
The cargo probe temperature reading is outside of --50 to 70°C (--58 to
158°F) range.
These alarms are for future expansion, and are not in use at this time.
The network data point is outside of its specified range. The DataCORD-
ER is configured by default to record the supply and return recorder sen-
sors. The DataCORDER may be configured to record up to 8 additional
network data points. An alarm number (AL78 to AL85) is assigned to each
configured point. When an alarm occurs, the DataCORDER must be inter-
rogated to identify the data point assigned. When a humidity sensor is
installed, it is usually assigned to AL78.
The Real Time Clock (RTC) backup battery is too low to adequately main-
tain the RTC reading.
An invalid date or time has been detected. This situation may be corrected
by changing the Real Time Clock (RTC) to a valid value using DataLINE.
A write of critical DataCORDER information to the EEPROM has failed.
An error has been detected in the process of writing daily data to the non-
volatile FLASH memory.
This alarm is for future expansion, and is not in use at this time.
The DataCORDER alarm queue is determined to be full (eight alarms).
3-27
DESCRIPTION
NOTE
NOTE
T-317