Philips LRC2410 Installation Instructions Manual page 5

8x20a relay control panel bacnet ms/tp enabled
Table of Contents

Advertisement

Double Pole Relays:
1.
Connect the 2 pole relay card CONTROL POWER INPUT to a 120 or 277 volt circuit, typically the same circuit connected
to the cabinet power supply.
2.
Connect a 120 or 277 volt, 30 amp maximum, 2 pole branch circuit breaker to the 2 pole relay terminal positions labeled
LINE.
3.
Connect a 2 pole load to the 2 pole relay terminal positions labeled LOAD. See Figure 6 for details.
Note: Factory wiring configures the 4 double pole relay outputs to correspond to RELAY buttons 1 - 4.
2 POLE RELAY CARD
CONTROL POWER
INPUT
COIL OUTPUTS
3 AND 4
Connect Loads - 4 Double Pole
COIL OUTPUTS
1 AND 2
BLUE
RED
COIL 1 & 2
NEUTRAL
WHITE
CONTROL
NEUTRAL
POWER
120/277
WHITE
COIL 3 & 4
NEUTRAL
BLUE
RED
Figure 6 - Load Connections, 4 Double Pole
CONNECT TO CIRCUIT
POWERING CABINET
POWER SUPPLY
COIL LINE
(BLUE)
LINE
LOAD
LINE
LOAD
COIL NEUTRAL
(WHITE)
LINE
LOAD
LINE
LOAD
COIL LINE
(RED)
COIL LINE
(BLUE)
LINE
LOAD
LINE
LOAD
COIL NEUTRAL
(WHITE)
LINE
LOAD
LINE
LOAD
COIL LINE
(RED)
LRC2410 Installation Instructions, Part No. CDCS000314 Rev. A 7/11
CONTROL
POWER INPUT
120/277
TYPICAL
2 POLE LOAD
WIRING
2 POLE
LOAD
2 POLE
CIRCUIT
BREAKER
30 AMP, 600V MAX
FACTORY WIRING
CONTRACTOR
SUPPLIED
WIRING
Page 5