Before You Start; Install Cabinet - Philips LRC2410 Installation Instructions Manual

8x20a relay control panel bacnet ms/tp enabled
Table of Contents

Advertisement

Before You Start

1.
Always disconnect all power.
2.
Install in accordance with the National Electrical
Code and any other codes which may apply.
3.
Use only as intended and at the listed voltage.
4.
All installation and service must be performed by
qualified personnel or service technicians.
5.
Do not install conduit where "No Conduit Entry" is
shown in Figure 1.
6.
Do not discard these instructions, this document is
a reference for installation, programming, operation,
and maintenance of the system.
7.
All installation and wiring information contained
herein is based on industry-accepted standards and
practices. This information is not meant to conflict
with or overrule any applicable codes or ordinances.
If any conflicts exist, please contact Philips Lighting
Controls before proceeding with the installation.
8.
Document all wiring, device terminations and
locations. This information will be necessary to
correctly configure the system and perform the
system start up .
9.
USE EXTREME CAUTION WHEN PERFORMING
MAINTENANCE ON THIS EQUIPMENT. HIGH
VOLTAGE IS PRESENT INSIDE THE ENCLOSURE!
Failure to follow any or all warnings and proper safety
procedures can cause severe injury or death, and/
or damage to the equipment.

Install Cabinet

1.
Mount the cabinet using the four holes provided
in the back of the enclosure. Refer to Figure 2 for
dimensions.
2.
Choose the desired location for line voltage and
low voltage conductor entry in the cabinet. DO NOT
install conduit where NO CONDUIT ENTRY is shown
in Figure 1.
ALL LINE VOLTAGE conductors must enter the
3.
cabinet on the right side (when facing) of the
enclosure, in the area shown in Figure 1.
ALL LOW VOLTAGE conductors must enter the
4.
cabinet on the left side (when facing) of the enclosure,
in the area shown in Figure 1.
5.
Remove ALL metal shavings and excess contaminants
from the enclosure before applying power to the
cabinet.
LRC2410 Installation Instructions, Part No. CDCS000314 Rev. A 7/11
Page 2
LOW VOLTAGE
CONDUIT ENTRY
AREA
LOW VOLTAGE
(CABINET
LOW VOLTAGE
ELECTRONICS)
WIRING GUTTER
COMPARTMENT
2"
LOW VOLTAGE
CONDUIT ENTRY
Figure 1 - Conduit and Cable Entry
15/16"
EXTERNAL
1 1/2"
FLANGE
14"
Figure 2 - Cabinet Dimensions
Semi-recessed mounting option:
Opening should be 14 5/8" wide, 14 1/16" high, and requires
3 3/8" wall depth minimum.
NO CONDUIT
ENTRY
LINE VOLTAGE
CONDUIT ENTRY
RELAY
(LINE VOLTAGE)
COMPARTMENT
2"
NO CONDUIT
ENTRY
BOTTOM VIEW
12"
12"
14 1/2"
15 13/16"
AREA
LINE VOLTAGE
WIRING GUTTER
LINE VOLTAGE
CONDUIT ENTRY
EXTERNAL
FLANGE
GROUND
LUG
INPUT
POWER
TERMINAL
BLOCK