Single Pole Relays:
1.
Connect a 120 or 277 volt, 20 amp maximum, branch circuit breaker to the output terminal block position labeled LINE.
2.
Connect a single pole load to the output terminal block position labeled LOAD. See Figure 5 for details.
Note: Factory wiring configures the 4 single pole relay outputs to correspond to RELAY buttons 1- 4.
Double Pole Relays:
1.
Connect the 2 pole relay card CONTROL POWER INPUT to a 120 or 277 volt circuit, typically the same circuit connected
to the cabinet power supply.
2.
Connect a 120 or 277 volt, 30 amp maximum, 2 pole branch circuit breaker to the 2 pole relay terminal positions labeled
LINE.
3.
Connect a 2 pole load to the 2 pole relay terminal positions labeled LOAD. See Figure 5 for details.
Note: Factory wiring configures the 2 double pole relay outputs to correspond to RELAY buttons 5 and 6.
2 POLE RELAY CARD
CONTROL POWER
INPUT
COIL OUTPUTS
LRC2410 Installation Instructions, Part No. CDCS000314 Rev. A 7/11
Page 4
Connect Loads - 4 Single Pole, 2 Double Pole
RELAY 1
RELAY 2
RELAY 3
RELAY 4
COIL OUTPUTS
5 AND 6
BLUE
COIL 1 & 2
NEUTRAL
WHITE
CONTROL
POWER
120/277
7 AND 8
COIL 3 & 4
NEUTRAL
Figure 5 - Load Connections, 4 Single Pole, 2 Double Pole
LINE
LOAD
LINE
LOAD
LINE
LOAD
LINE
LOAD
COIL LINE
(BLUE)
RED
LINE
LINE
NEUTRAL
LINE
LINE
COIL LINE
(RED)
N
TYPICAL BRANCH CIRCUIT
AND SWITCH LEG
20 AMP MAX
CONNECT TO CIRCUIT
POWERING CABINET
POWER SUPPLY
LOAD
LOAD
TYPICAL
COIL NEUTRAL
2 POLE LOAD
(WHITE)
WIRING
LOAD
LOAD
30 AMP, 600V MAX
CONTROL
POWER INPUT
120/277
FACTORY WIRING
CONTRACTOR
SUPPLIED
WIRING
2 POLE
LOAD
2 POLE
CIRCUIT
BREAKER

Hide quick links: