E. EXHAUST REQUIREMENTS
should be
be
CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCTWORK CAN
CREATE A POTENTIAL FIRE HAZARD.
CAUTION: DRYER MUST BE EXHAUSTED TO THE OUTDOORS.
IMPORTANT: It is recommended that exhaust or booster fans not be used in the exhaust ductwork
system.
should be
should be
ALL
must be
should be
IMPORTANT: When connecting ductwork to the dryer exhaust duct, be sure that when screws are
used they DO NOT restrict the operation (both opening and closing) of the damper.
NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible
materials, the opening must be 2-inches (5.08 cm) larger than the duct (all the way around).
The duct must be centered within this opening.
IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust
ductwork.
IMPORTANT: Exhaust back pressure measured by a manometer at the dryer exhaust duct area must
be no less than 0 and must not exceed 0.3 inches (0.74 mb) of water column
(W.C.).
11
must
should be
should be