17.5.12. Compressor Rotation Failure (F14)
Malfunction Decision Conditions:
A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit.
Malfunction Caused:
1. Compressor terminal disconnect.
2. Faulty outdoor unit PCB.
3. Faulty compressor.
Abnormality Judgment:
Continue 4 times in 20 minutes.