17.5.10. Indoor Freeze Prevention Protection: Cooling (H99)
Error code will not display (no OFF/ON Control Panel LED blinking) but store in EEPROM
Malfunction Decision Conditions:
Freeze prevention control takes place (when indoor pipe temperature is lower than 0°C)
Malfunction Caused:
1. Dust accumulation on the indoor unit heat exchanger.
2. 2/3 way valve closed.
3. Refrigerant shortage (refrigerant leakage).
4. Clogged expansion valve or strainer.
5. Faulty indoor pipe temperature sensor.
6. Faulty indoor unit PCB.