17.5.20. Outdoor High Pressure Switch Abnormal (F27)
Malfunction Decision Conditions:
During compressor stop, and outdoor high pressure switch is remain opened.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty switch.
3. Faulty outdoor unit PCB.
Abnormality Judgment:
Continue for 1 minute.