17.5.5. Outdoor High Pressure Abnormality (H64)
Malfunction Decision Conditions:
During operation of heating, when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty outdoor unit PCB.
Abnormality Judgment:
Continue for 5 seconds (but no judgment for 5 minutes after compressor startup/restart).