Application Considerations; Clearance Requirements; 180 Degree Blower Rotation; Low Ambient Cooling - Trane 7½ - 20 Tons Manual

Split system heat pumps
Table of Contents

Advertisement

Application of this product should be
within the catalogued airflow and
performance considerations.

Clearance Requirements

The recommended clearances
identified with unit dimensions
should be maintained to assure
adequate serviceability, maximum
capacity and peak operating
efficiency. Actual clearances which
appear inadequate should be
reviewed with a local Trane
Representative.
180° Blower Rotation
The 5, 7½ and 10 ton air handler
blower section can be rotated 180° to
change the discharge pattern. This
modification must be done in the
field and requires an additional kit.
See unit installer's guide.

Low Ambient Cooling

As manufactured, these units can
operate to 50°F in the cooling mode
of operation. An accessory head
pressure control will allow operation
to 0°F outdoor ambient. When using
these units with control systems
such as bypass changeover Variable
Air Volume, make sure you consider
the requirement for a head pressure
control to allow low ambient
cooling.
6

Application Considerations

Figure 5.
Typical Horizontal Air Handler Application
Figure 6.
Typical Split System Application
SSP-PRC001-EN