Table 8.
Electrical Service Sizing Data (continued)
Allow-
Electrical
Voltage
Model
Charac.
Range
380/415/50/
342-418/
RAUC-C609
3XL
373-456
1. Electrical data is for each individual motor.
2. Max Overcurrent Protection device permitted by N.E.C. 440-22 (1993) is 225% of the largest compressor motor RLA plus the remaining motor RLA
and FLA values.
3. Minimum circuit ampacity is 125% of the largest compressor motor RLA plus the remaining motor RLA and FLA values.
4. Recommended dual element fuse size is 150% of the largest compressor motor RLA plus the remaining motor RLA and FLA values.
5. Kw values are taken at conditions of 45ºF saturated suction temperature at the compressor and 95ºF ambient.
6. Local codes may take precedence.

Field Installed Control Wiring

Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before installing any connecting wiring, refer to
locations provided on the unit. Install appropriately sized control wiring for the 115 volt electrical
components as required by the application.
Since the unit-mounted 115V control power transformer (1T1) is provided on all units, it is not
necessary to run a separate 115 volt control power source to the unit.
Note: 200/230 Volt units are shipped with transformer 1T1 wired for 200 volt operation. If the unit

Controls Using 115 VAC

Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Install appropriately sized 115 volt control wiring for the electrical components as required by the
application.
These components may include:
SS-SVX09A-EN
Unit Characteristics
Max.
Over-
Dual
able
Min.
current
Element
Circuit
Protect
Fuse
Amp
-ion
122
125
WARNING
is to be operated on a 230 volt power supply, rewire the transformer as shown on the unit
schematic.
WARNING
hot gas bypass solenoid wiring;
supply fan interlock and control circuit;
system control switch wiring ("No Control" units);
step controller wiring ("No Control" units);
chilled water pump interlock wiring (EVP units);
chilled water flow switch wiring (EVP units);
outside air thermostat wiring (EVP units):
Condenser Fan Motor
Rec.
KW
FLA
Size
(Ea) No HP
(Ea)
125
0.75
6
1.0
1.7
Figure 3
Compressor Motor
RLA
RLA
LRA
(Ea)
(Ea)
(Ea)
LRA
10
15
10
(Ea)
No
Ton
Ton
Ton
9.2
4
_
26.2
_
to
Figure 8
for the electrical access
Installation
LRA
Kw
Kw
(Ea)
(Ea)
(Ea)
15
10
15
Ton
Ton
Ton
174.0
_
16.4
49