Final System Setup - Trane RAUC-C20 Installation Operation & Maintenance

Remote split system units air cooled condensing units and evp chillers
Table of Contents

Advertisement

System Start-Up

Final System Setup

After completing the Pre-start and Start-up procedures outlined in the previous sections, perform
these final checks before leaving the unit:
[ ] Turn the 115 volt control circuit switch 1S2 "Off" .
[ ] Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer
to the programming instructions for the specific panel.
[ ] Verify that the "System" selection switch and the "Fan Mode" selection switch at the Remote
panel is set correctly.
[ ] Verify that the "System" control switch for the supply fan or the chilled water pump is "On" .
[ ] Set the correct "Operating Temperature" for the system at the system controller. Refer to
Figure 17
[ ] Turn the 115 volt control circuit switch 1S2 "On" . The system will start automatically once a
request for cooling has been given.
[ ] Verify that all exterior panels and the control panel doors are secured in place.
Table 17. Recommended Operating Setpoints
Zone Thermostat (CV units
Note: "No Controls" Units See System Engineer
102
for the recommended control set points for the appropriate control option.
Control
Discharge Air
Controller
(VAV units only)
Leaving Fluid Setpoint
Chiller Control
(EVP units only)
Freezestat
Low Limit Solution Temperature
only)
Control Setting
Set at design discharge (supply) air temperature;
Supply Air Setpoint
Set at maximum amount of allowable reset for supply
Reset Setpoint
Control Band
Reset Setpoint
Control Band
Zone Setpoint
Recommended Setting
minimum setting = 55
air setpoint.
o
Set at 6
F Minimum Setpoint
Set at design leaving chilled water temperature
o
(typically) 44
Set at maximum amount of allowable reset for
leaving fluid setpoint.
o
Set at 6
F Minimum Setpoint
o
Set at 5
F Minimum above the Chilled Solution
Freeze Temperature
Set at desired space temperature.
o
F
F
SS-SVX09A-EN