INDOOR UNIT OUTDOOR UNIT GAS SIDE 3-WAY VALVE Muffler Di s charge HEAT EXCHANGE (EVAPORATOR) Suction Accumlator COMPRESSOR HEAT EXCHANGE (CONDENSER) LIQUID SIDE 2-WAY VALVE Strainer Capillary Strainer COOLING INDOOR UNIT OUTDOOR UNIT GAS SIDE 3-WAY VALVE 4-Way valve Muffler Di s charge HEAT EXCHANGE...
Sound Level Test condition Test value 60Hz Models(Cooling only -Heat pump) Unit Model Indoor Sound Pressure level (dB(A)) Number Outdoor Indoor 2TWK0509G1000AA 2MWW0509G1000AA 2TWK0512G1000AA 2MWW0512G1000AA 2TWK0512G9000AA 2MWW0512G9000AA 2TWK0518G1000AA 2MWW0518G1000AA 2TWK0524G1000AA 2MWW0524G1000AA 2TWK0530G1000AA 2MWW0530G1000AA 50Hz Models(Cooling only -Heat pump) Model Indoor Sound Pressure level (dB(A)) Unit Number Outdoor...
Operating Functions Operation of remote controller Temperature parameters • Room set temperature (T set) • Room ambient temperature (T amb) Fundamental functions After powered on, no matter when the compressor is started, the time interval between two startups cannot be less than 3 minutes. COOL mode The condition and process of cooling •...
Page 48
Overcurrent protection If total current is high, the compressor will run in limited or dropped frequency. When total current goes on rising over the stated value, the compressor will stop, the outdoor fan will delay 30 seconds to stop. DRY mode The condition and process of drying •...
Stop heating Tset Original running state Tset Start heating Tamb 3min Compressor Outdoor fan Indoor fan 2min 2min Reversal valve The condition and process of defrosting When frost is detected in the condenser, the system will enter into defrosting state. When defrosting starts, the compressor and indoor fan will stop, and the outdoor fan and four-way valve will delay 30 seconds to stop.
Page 50
TEMP . setting button Each time TEMP + or TEMP - button is pressed, the set temperature will be increased or decreased by 1ºC. Adjusting range is 16~30ºC . In AUTO mode, this button does not function. AUTO key When the unit is stop, press AUTO key, the unit will run under AUTO mode and the swing motor starts.
Page 51
Indoor fan control Use the remote controller to set the indoor fan running at HIGH, MED or LOW speed. At this time the fan will run at high, medium or low speed. It can also be set to AUTO and the indoor fan will select fan speed(HIGH, MED or LOW) automatically according to ambient temperature.
Page 52
Compressor discharge temperature protection When discharge temperature is too high to over the stated value, the compressor will stop, and When discharge temp. resume normal and the compressor has stopped for 3 minutes, the unit will resume its original operating status. Communication malfunction When not receiving correct signal for 3 minutes, the unit has communication malfunction and the outdoor unit stops, it is the same as normal stop when meeting the set temp.
Page 54
temp. sensor clasp 4. Remove front case Unscrew the 6 tapping screws fixng the front panel and turn the front case backward to remove it. screw clasp 5. Remove electric box screw Unscrew the 2 screws fixing the electric box Pull out the wiring terminal of motor and then un- screw the 3 screws fixing electric box.Lift the ele- ctric box to remove it.
Page 55
screw 7. Remove motor and cross flow fan Unscrew the screws fixing the motor press plate of motor and then the screws connecting the mo- tor and cross flow fan to separate and remove them. screw screw...
Removal Procedure of Outdoor Unit Cable Cross Plate sub-assy 1. Remove top cover and the Cable Cross Plate sub- assy Unscrew the screw on the handle and pull the top cover Cable Cross Plate sub-assy forcibly downwards to re- move it. Unscrew the 3 screws fixing the top cover to remove it.
Page 57
4. Remove electric box cover Unscrew the 2 screws fixing the electiric box. Pull theelectric box upwards and unplug the plug-in line to remove the electric box. screws 5. Remove axial flow fan Unscrew the nut and remove the washer fixing the axial flow fan and then pull it out.
Page 58
7. Remove electronic expannsion valve Unsolder the weld spots of eletronic expansion valve connecting with other pipelines to remove it. electronic expannsion valve 8. Remove gas valve and liquid valve Unscrew the 2 screws fixing the gas valve and unsolder the weld spots of gas valve and suction pipe to remove the gas valve.
Troubleshooting WARNING Hazardous Service Procedures! The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures. Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing.
Page 60
Figure Troubleshooting chart Adjust the set temperature Improper setting of temperature Check the estimated load of cooling (heating) Whether cooling (heating) load is proper Vacuumize after leakage detection Leakage or shortage of refrigerant and leakage repair. Charge refrigerant according to specification. Leakage occurs between high and Replace the compressor low pressure inside compressor...
Page 61
Figure Troubleshooting chart Abnormal power supply of outdoor unit Check the circuit according to circuit diagram When unit is Damage of outdoor main control board Replace the main control board cooling or heating, both compressor and outdoor fan don't Breakage of outdoor power module Replace the power module Improper setting of temperature Adjust the set temperature...
Page 62
Figure Troubleshooting chart Blockage or breakage of drainage hose Replace the drainage hose Water leakage Wrap of refrigerant pipe connector is not Re-wrap and make it tight tight enough Fan of indoor unit contacts other parts Adjust fan location There is foreign substance in indoor unit Take out the foreign substance Compressor shakes too much Adjust support washer of the compressor and...
Page 63
Figure Compressor is too hot Compressor too hot, Check whether the outdoor unit is not mounted just start and stop at Change the mounting position properly such as outlet blockage; bad ventilation once, or the stop or directly under sunlight often occur Ambient temperature is too high For safe use...
Page 64
Analysis or handling of some of the malfunction displays: System high pressure protection (E1): Handling method: check the system pressure, or replace the PCB. Anti-freezing protection (E2): The unit will recover later, no correction is needed. Compressor discharge protection (E4): Possible reasons: shortage of refrigerant;...
Page 65
Figure Troubleshooting Module Protection (H5) Check if the voltage between power module P and N is too low and if the current is too high. In normal condition, voltage between P and N should be about 320V. Abnormal Check power supply circuit of outdoor unit (if PTC resistance Normal rectifying bridge, reactor, capacitance etc.
Page 68
Literature Order Number Date Supersedes www.trane.com For more information, contact your local Trane Trane has a policy of continuous product and product data improvement and reserves the right to office or e-mail us at comfort@trane.com change design and specifications without notice.