Siemens REV23.03RF User Manual page 12

Self-learning room temperature controller receiver
Table of Contents

Advertisement

LED_2 is always off
LED_2 is always on
LED_2 flashes always
LED_2 flashes briefly
7. Finishing
mounting of
REV-R.03/1
Notes
Commissioning
controller/transmitter
REV23RF
(previous model)
and receiver
REV-R.03/1
12/17
Building Technologies
HVAC Products
Orange on
Controlled device OFF
Orange off
Orange on
Controlled device ON
Orange off
Learning mode active
Orange on
Orange off
Reption of control telegram
a) Switch off power
b) Mark location where REV-R.03/1 is currently fixed
c)
If necessary loosen wiring
d) Mount receiver at location marked before, wire completely and close housing
e) Switch on mains power
In the event of a power failure at the REV-R.03/1, the relay will be deenergized.
If in normal operation REV-R.03/1 does receive for more than 25 minutes a very
weak or no control telegram from REV23.03RF, LED_1 starts to flash in red.
If control telegram is still understood correctly, receiver continues with normal op-
eration. If control telegram is not understood anymore, relay remains in last position
being switched to before.
As soon as REV-R.03/1 does receive any correct control telegram from
REV23.03RF again, receiver continuous with normal operation
In case of error, REV-R.03/1 switches off relay approximately 60 minutes after re-
ception of last correct control telegram. The controlled device is also switched off
and LED_1 flashes in red.
As soon as REV-R.03/1 does receive any correct control telegram from
REV23.03RF again, receiver continuous with normal operation
If instead of REV23.03RF the previous model REV23RF shall be linked with
REV-R.03/1, follow the procedure below:
− Follow steps 1 ... 3b (same as commissioning with REV23.03RF)
− Instead of step 3c, press buttons SET and RESET simultaneously for approximately
3 seconds until orange LED_2 starts flashing slowly and continuously: Receiver is
now in learning mode for previous controller type REV23RF
− Change temperature setpoints at REV23RF to force transmission of a control tele-
gram: As soon as orange LED_2 flashes fast and shortly REV23RF and REV-R.03/1
are linked together
− If the orange LED_2 is steady on, the relay is energized (= controlled device ON)
− If the orange LED_2 is dark, the relay is deenergized (= controlled device OFF)
− Continue to step 7
Raumtemperaturregler REV23.03RF
CE1N2265en
22.02.2006