Ravel RE-2504 Installation, Commissioning & Operating User Manual page 42

Automatic fire alarm control panel
Table of Contents

Advertisement

<Prev
xxx – represents silence time; yy – represents feature number
4.2.1.2.5
Silence Inhibit:
The
silencing of Notification Appliance Circuits, using the
Silence switch or Reset switch, for the amount of time
corresponding to the selected option, after the
NAC's are activated. The factory default for this
feature is 'disabled'. Press '#' to toggle between
enabled / disabled option. The Silence inhibit timing
can set 1 to 999 seconds. After setting the required
time press Enter key to accept the time. When you
enter into this mode the screen will be as below.
xxx – represents silence time; yy – represents feature number
4.2.1.2.6
AC Loss Delay:
When AC power is lost, the control panel
trouble relay will activate. The factory default option
for this feature is Enabled, the trouble relay
activation on AC loss after the time delay setting.
Relay activation may be delayed by selected as
shown in LCD screen display. Press '#' to toggle
between enabled / disabled option. The AC Loss
Delay timing can set 001 to 999min. After setting the
required time press Enter key to accept the time.
Auto Silence
Enabled: XXX Secs.
yy
Silence
Inhibit
Silence_Inhibit
Enabled:
XXX Secs.
<Prev
yy
41
Next>
feature
prevents
Next>
RE / DD / UM / 2508 V1.2- 01
the