Ravel RE-2504 Installation, Commissioning & Operating User Manual page 37

Automatic fire alarm control panel
Table of Contents

Advertisement

X = Zone Number
Y = F / S / A / W / D mode.
F – Fire, S – Supervisory, A – Alarm Verification, W – Walk
test, D - Disable
The zone is selected by using the right / left arrow
keys, the mode can change using the '#' key. Then
press the Enter key to accept the changes. This process
can be continued in case of other zone to be
changed.
Note:
1.
At the time of Fire/Supervisory events in a fire /
supervisory mode set zone, that particular zone
mode can only be disabled.
2.
To go back to the previous menu or come out of
the menu configuration press '*' key.
Fire Mode: In this mode the zone will be in normal
condition to detect the fire with detectors and manual
call point (normally open devices). This mode is
represented as 'F' at the time of setting.
Supervisory Mode: In this mode the zone will detect
normally open devices. The optional feature of
selecting resettable / latching mode. This mode is
represented as 'S' at the time of setting.
Disable Mode: In this mode the zone is disabled with
loop voltage cut off. This mode is represented as 'D' at
the time of setting.
Avoid disabling any zone unless it is really
Note:
essential.
36
RE / DD / UM / 2508 V1.2- 01