Page 3
Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Page 4
Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Page 5
Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Chapter 1: Introduction This manual is intended as a complete guide to the RE 150D model Conventional Fire Control Panel. User operating Instructions are provided in the first part of this manual. This is followed with sections describing installation and commissioning procedures and full technical details are provided.
As a minimum, the user shall record any incident and inform the service organization, who may be required to retest the system. The user's responsibilities are described fully in IS 2189: 1999. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Note: The control panel case should be cleaned periodically by wiping with a soft, damp cloth. Do not use any solvents. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Twin RED LED indication for fire. Zone Isolation facility with loop voltage cut off. Earth Fault with Audio and Visual Indications. Supervised Sounder 24v DC output for External notification devices (Sounder, Bell, etc.). 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Battery Low – Yellow Common Hooter Fault – Yellow AUX. Isolate – Yellow Walk Test – Yellow Silence – Yellow Zone Fire – Red Zone Fault – Yellow Zone Isolate – Yellow 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
3 seconds for Detectors and MCPs, Then voltages are put on to the loop. Note: The zone loop voltage will cut off only in fire condition during reset. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
The panel also has a built in battery provision to accommodate 2 Nos. of 12v, 7Ah batteries (Up to 12 Zone). The front side of the panel consists of the following, Tactile switches. LED indications 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 0- 50° C/32-120° F. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Page 17
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
When the installation of all the cables has been completed, clean the interior of the enclosure ensuring all masonry debris and drilling swords are removed. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
2-wire, 24 volt smoke detectors. It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any zone. Zone Circuit – Class B 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
30 VDC and 2.0 amps @ 30 VAC. Relay connections may be power-limited or nonpower-limited, provided that a minimum of 0.25" is maintained between conductors of power-limited and nonpower-limited circuits. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
LAMP TEST Key: This key is used to check the all LED’s in panel is in good condition with continuous buzzer tone. SELECT Key: This key is used to select the particular zone for the self test and isolation purpose. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
BATTERY LOW: Whenever the backup battery voltage goes below the 21v, the low battery LED will be illuminated and it also indicated with toggle Buzzer tone. CHARGER ON: This LED indicates the condition of charging circuit. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
When the control panel detects Fire via the Detector / MCP, the corresponding ZONE FIRE red LED will be illuminated. At the same time hooter, potential free contact (Fire Relay) and local buzzer (continuous tone) will be activated. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
The OFF status indicates the zone is in monitoring condition. For Zone Isolation the follow the steps given below. a. Press the ‘select’ key zone1 selects first with indication of isolate LED blinking. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
3 seconds the panel will get automatically silenced. After 6 seconds of silence, the panel will go to reset. This reset is done for only that particular zone. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
To test a particular zone, follow the procedure as below 1. Press the ‘select’ key zone1 selects first with indication of isolate LED blinking. 2. Press ‘select’ key consequently until select the zone which is to be test. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
X = S (0.0772A) x 48 Hrs. = 3.7056 Y = F (0.94A) x 1 Hrs. = 0.94 AH = X+ Y = (3.7056+ 0.94) X 1.2 = 5.57472Ah 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
IN4007 each hooter’s +ve loop is connected to 1N 4007 diode’s Hooter cathode and the (NAC) hooter –ve loop connected to the anode of 1N 4007. 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
) - 18 AWG 24 VDC limitation set by annunciators allowed from (0.75 mm resettable, 1.2 volt and other supply source nonresettable maximum accessories to end of any line drop branch 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Institute of Electrical Engineering End Of Line Printed Circuit Board Central Processing Unit Manual Call Point S.Nos Serial Numbers milli Ampere killo grams CO,NO,NC- Common, Normally Open, Normally Closed 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
General Arrangement Diagram: 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Page 32
This is to certify that the following items are tested and checked. Microprocessor Based Conventional Fire Alarm Control Panel. Model No.: RE – 150D Serial No.: No. of zones: For RAVEL ELECTRONICS PVT.LTD, Q.C. – Engineer Tested By 6/28/2011 DOC.NO.: 150D - 1 P/N RE 150D Rev. No. 1...
Page 33
RE – 150D Serial No.: Ravel Electronics warrants each product to be free from defects in material and workmanship. This obligation is limited to servicing or part returned to the company for that purpose and making good any parts thereof which shall be within warranty period, returned to the company under a written intimation and which to the company’s satisfaction to be found defective.