  • Page 1 RE-900 Fire Alarm Control Panel Installation, Commissioning & Operating user Manual...
  • Page 2: Fire Alarm System Limitations

    • Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before reaching the detector. RE / DD / UM / RE-900 1.0-0...
  • Page 3 Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. RE / DD / UM / RE-900 1.0-0...
  • Page 4 Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. RE / DD / UM / RE-900 1.0-0...
  • Page 5: Notes

    NOTES: RE / DD / UM / RE-900 1.0-0...
  • Page 6: Table Of Contents

    5.3.2 ZONE FIRE: ..............................45 5.3.3 ZONE DISABLE/W.T: ............................46 6: S : ...............................48 HAPTER ERVICING INSTALLATION/REPLACEMENT OF PCB: ......................48 7: T ............................50 HAPTER ROUBLE HOOTING 8: A ..............................51 HAPTER BBREVATION RE / DD / UM / RE-900 1.0-0...
  • Page 7: Chapter 1: Introduction

    EOL device is used. Installation The panel is easy to install and operate. Control functions Programming functions are enabled by using password. The panel fascias are retained by tamper-proof screws. RE / DD / UM / RE-900 1.0-0...
  • Page 8: Fire Alarm Procedures

    As a minimum, the user shall record any incident and inform the service organization, who may be required to retest the system. The user's responsibilities are described fully in IS 2189: 1988. RE / DD / UM / RE-900 1.0-0...
  • Page 9: Routine Testing

    Note: The control panel case should be cleaned periodically by wiping with a soft, damp cloth. Do not use any solvents. RE / DD / UM / RE-900 1.0-0...
  • Page 10 Mother Board Terminals and connectors Power Supply Board Terminals and connectors RE / DD / UM / RE-900 1.0-0...
  • Page 11 RE / DD / UM / RE-900 1.0-0...
  • Page 12: Chapter 2: Product Description

    Fire and one relay for fault. And also communication port RS485 to interface with remote annunciator. This panel is field programmable via the front panel keypad. It supervises all wiring, AC voltage and Battery level. RE / DD / UM / RE-900 1.0-0...
  • Page 13: Product Features

    Resettable / Steady 24V D.C. Output. RS 485 Communication facility (Optional). TCP/IP (Optional) facility. Walk Test facility. Zone Wise Sounder/Contact via RS 485. All field wiring circuits are Power limited except 110 - 220v AC and Battery. RE / DD / UM / RE-900 1.0-0...
  • Page 14 All field wiring circuits are supervised. Zone Isolation facility with loop voltage cut off. Earth fault annunciation facility at 0 ohms. Programmable AC loss delay. Programmable Trouble reminder. Peer to Peer Networkable Repeater connectivity via Rs485. RE / DD / UM / RE-900 1.0-0...
  • Page 15: Specification

    Normal Operating Voltage: 14 - 24 VDC Alarm Current: 15 – 35mA threshold Short Circuit Current: 45mA Maximum Loop resistance: 100 ohms Maximum End-Of-Line Resistor: 4K7, 1/2 watt Standby Current: 7 mA (2.5 mA for Detectors) RE / DD / UM / RE-900 1.0-0...
  • Page 16 End-Of-Line Resistor: 4K7, 1/2 watt Common Relays: Type : Form C No of Relays Relay Contact Rating : 2Amps @ 30VDC 0.5Amps @ 125VAC Power factor : 1.0 RS485 Communication Port Max. Distance: 1.5Km Max. RE / DD / UM / RE-900 1.0-0...
  • Page 17: Control And Indications

    To reset the particular zones in Fire alarm or Latched Supervisory condition. User or Admin password protected. Possible to access only after silence in alarm condition. EVACUATE: To activate External NACs Manually. User or Admin password protected. RE / DD / UM / RE-900 1.0-0...
  • Page 18: Indications

    LED indications except system on and system fault. 2.3.2.2 Local Buzzer A piezo buzzer provides separate and distinct sounds for alarm, trouble and supervisory conditions: Alarm – Continuous Fault – pulse 0.5sec ON and 5sec OFF RE / DD / UM / RE-900 1.0-0...
  • Page 19: Mechanical Construction

    Std.) 20no’s of knockouts are given for cable entry at the top of the cabinet. The lockable hinged door is provided to access the inside the cabinet. The panel also has sufficient space to accommodate 2 Nos. of 12v, 7Ah batteries. RE / DD / UM / RE-900 1.0-0...
  • Page 20 Internal Arrangement RE / DD / UM / RE-900 1.0-0...
  • Page 21 Components Master Board (RE-900-16Z-MB) The Master board contains the primary components and wiring interface connectors. Display Board (RE-900-DISP-R1.1)The Display Board contains the system CPU, LED Display, LCDunit and Control keys. Display Board (RE-900-DISP-R1.1) RE / DD / UM / RE-900 1.0-0...
  • Page 22 Power Supply Board (RE-900-PS) RE / DD / UM / RE-900 1.0-0...
  • Page 23: Chapter 3: Installation

    Therefore, it is recommended that this system peripherals installed environment with a nominal room temperature of 15- 27° C/60-80° F. RE / DD / UM / RE-900 1.0-0...
  • Page 24 Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. RE / DD / UM / RE-900 1.0-0...
  • Page 25 2- wire, 24 volt smoke detectors. It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any zone. RE / DD / UM / RE-900 1.0-0...
  • Page 26 24v DC out Terminals. Sounder Circuits The RE - 900 provides Notification Appliance Circuits (NAC) standard as Class B. This circuit is capable of a maximum of 0.2 amps of current per zone. RE / DD / UM / RE-900 1.0-0...
  • Page 27 The control panel provides three Form-C relays rated for 2.0 amps @ 30 VDC and 2.0 amps @ 30 VAC. Relay connections may be power-limited or nonpower-limited, provided that a minimum of 0.25" is maintained between conductors of power-limited and nonpower- limited circuits. RE / DD / UM / RE-900 1.0-0...
  • Page 28: Chapter 4: Programming Instructions

    24 V O/ P <<Ste ady >> <<Ste ady >> [24 V O/P*] 1 . Set tin gs 2 . Fe atu re s 3 . A dva nce d [ Common] RE / DD / UM / RE-900 1.0-0...
  • Page 29 T ime: hh : mm : ss [# Edit] Sav e] [R TC] [RTC] AC Loss De lay AC Loss De lay Enable d : 120 Min Disable d Save ] Save ] [Fe ature 1 [Fe ature1 RE / DD / UM / RE-900 1.0-0...
  • Page 30 Re - Ne w Pa ssw ord [Ch g Co nf ig Pas s] [Chg Conf ig Pass ] Upda ted [Chg Conf ig Pa ss] Fac tor y D ef ault Rec ove ring ..RE / DD / UM / RE-900 1.0-0...
  • Page 31 [Chg Adm Pass] [chg Usr1 Pass] Re-Type New? Re-Type Ne w? ***** New Password updated [chg Usr1 Pass] Pre ss '#' to chge Re-Type New? **** New Password updated Pre ss '#' to chge RE / DD / UM / RE-900 1.0-0...
  • Page 32: Programming

    Alarm, Supervisory, Fault, Silence Reset and etc., with Real Time Clock. By pressing the key ‘2’ from View menu brings the History mode. The history mode provides the following event filtering option, RE / DD / UM / RE-900 1.0-0...
  • Page 33 It is shown as below: 1. Mode 2. Location Program 3. Wiring [Zone] 4.2.2.1.1 Mode By selecting the number 1 in the keypad, it enters into the Mode screen. It Displays as follows. RE / DD / UM / RE-900 1.0-0...
  • Page 34 The Style of class-B can be changed as Style-B or Style- C by pressing ‘#’ key from the panel key pad. When you enter into this mode the screen will be as below. Type: Wiring Class : B (# Edit) (wiring) RE / DD / UM / RE-900 1.0-0...
  • Page 35 Sounders will be evacuated simultaneously. To change the option press ‘#’ key to toggle between the options Steady, Temporal, Synchronized. The NAC’s should be in off condition to change the options. RE / DD / UM / RE-900 1.0-0...
  • Page 36 By selecting the number 4 in the keypad, it enters into the Common screen. It Displays as follows. 1. Settings 2. Features 3. Advanced [Common] By selecting the number 1 in the keypad, it enters into the Setting mode. It Displays as follows. RE / DD / UM / RE-900 1.0-0...
  • Page 37 1. User 1 4. User 4 2. User 2 5. User 5 3. User 3 [Chg Pass] RE / DD / UM / RE-900 1.0-0...
  • Page 38 ‘enter’ key from the change Admin Password screen, system enters into the Admin Password change mode. The display screen of this mode showed as below. The Default Password is”54321”. The Password should be five digit. RE / DD / UM / RE-900 1.0-0...
  • Page 39 After setting the required time press Enter key to accept the time. The default time is 120 Seconds. When you enter into this mode the screen will be as below. 9. AC Loss Delay <120 (Min)> RE / DD / UM / RE-900 1.0-0...
  • Page 40 By selecting the number 1 from the network screen, the system enters into the network address changing mode. In this mode the address of the panel shall be changed using the alphanumeric key RE / DD / UM / RE-900 1.0-0...
  • Page 41 By selecting the number 2 from the advanced screen, the system enters into the password control. In this stage user & Advance password can be reset. After entering into this mode, screen will as shown below. RE / DD / UM / RE-900 1.0-0...
  • Page 42 16 zone RE – 900- 16Zone, 32Zone RE-900 Fire Alarm Panel Model: RE-900 Ver 1.0 16 Zone Panel Note: Version shown is software version. RE / DD / UM / RE-900 1.0-0...
  • Page 43: Chapter 5: Operating Instructions

    3 seconds for Detectors and MCP’s, Then voltages are put on to the loop. RE / DD / UM / RE-900 1.0-0...
  • Page 44: Indications

    Buzzer tone. The LCD Display as shown in the figure 22, ‘Mains fail’ will be displayed in the fault screen. Fault [ x/y ] Type of Fault x – n no. of fault; y – Total no. of fault. Figure – 22 RE / DD / UM / RE-900 1.0-0...
  • Page 45 ZONE FAULT: This fault LED will glow when there is an open or short or earth fault in that particular zone. ZONE DISABLE/W.T: This zone wise LED glows steadily in disabled condition and blinking in the Walk test mode. RE / DD / UM / RE-900 1.0-0...
  • Page 46: Operation

    And in the output to main panel shows Fire resistance (560 Ω), hence in the main panel where this sector panel is connected shows fire. RE / DD / UM / RE-900 1.0-0...
  • Page 47: Zone Disable/W.t

    LED indicates the zone is in walk test mode. In LCD the suppressed events are viewed in suppressed events from menu screen. Fault [XX/YY] Zone X Disabled RE / DD / UM / RE-900 1.0-0...
  • Page 48 In other zone gets fire, the walk test mode automatically removed. Restoral: When the zone restored to normal condition from disable / Walk test mode, the zone which are all in disable/W.T mode the corresponding LED’s goes off. RE / DD / UM / RE-900 1.0-0...
  • Page 49: Chapter 6: Servicing

    Mounting position for Main Circuit board (RE – 900 – 16Z – MB): Cable Entry Knock out Mounting Hole Mounting Hole 12V 12AH Battery 12V 12AH Battery RE / DD / UM / RE-900 1.0-0...
  • Page 50 Mounting position for Display board (RE – 900 – DISP – R1.1): Mounting Hole Mounting Hole Mounting position Display board – – Cable Entry Knock out 12V 12AH Battery 12V 12AH Battery RE / DD / UM / RE-900 1.0-0...
  • Page 51: Chapter 7: Trouble Shooting

    If hooter is non- polarized, then ensure each hooter’s +ve loop is connected to 1N 4007 diode’s cathode and the hooter –ve loop connected to the anode of 1N 4007. RE / DD / UM / RE-900 1.0-0...
  • Page 52: Chapter 8: Abbrevation

    Ampere per hour Institute of Electrical Engineering End Of Line Printed Circuit Board Central Processing Unit Manual Call Point S.No Serial Numbers milli Ampere kilo grams C,NO,NC - Common, Normally Open, Normally Close. RE / DD / UM / RE-900 1.0-0...
  • Page 53 Ravel Electronics Pvt Ltd., 150A, Electronic Industrial Estate, Perungudi, Chennai – 600096, India. Web: www.ravelfire.com marketing@ravelfire.com Email: RE / DD / UM / RE-900 1.0-0...